Transfer Time (Line Power to
Battery Mode)
Dip-switch selectable 20 millisecond (full cycle) / 10 millisecond (half-cycle) transfer times which are compatible with
many computers, servers and networking equipment - verify transfer time compatibility of loads for UPS applications
Low Voltage Transfer to Battery
Power
In 230V AC "auto" mode, inverter/charger switches to battery mode as line voltage drops to 170V AC (user
adjustable to 180V). In 208V AC "auto" mode, inverter/charger switches to battery mode as line voltage drops to
165V (user adjustable to 175V)-see manual
High Voltage Transfer to Battery
Power
In 230V AC "auto" mode, inverter/charger switches to battery mode as line voltage increases to 260V (user
adjustable to 270 - see manual), In 208V AC "auto" mode, inverter/charger switches to battery mode as line voltage
increases to 235V (user adjustable to 245V-see manual)
SPECIAL FEATURES
Load Sensing
Optional load sense function enables automatic inverter shutoff and startup as connected equipment is powered off
and on. Front panel load sense potentiometer can be set to shutoff or turn on inverter power in response to loads of
any level, up to 150 watts.
Remote Control Capability Yes
TVSS Grounding Main grounding lug connects inverter/charger to earth or vehicle chassis ground
CERTIFICATIONS
Certifications RoHS compliant
WARRANTY
Product Warranty Period (Worldwide) 2-year limited warranty