User Manual

6
Select Battery Charger-Limiting Points—OPTIONAL
“Most Limiting” (#B2 & #B1 Up):
Charger-limiting takes effect the moment
any 120V AC load is applied; charger
output falls gradually from full output at
no120Vloadpassingthroughtonooutput
at full load.
“Less Limiting” (#B2Up&#B1Down):
Charger-limiting begins when the Inverter/
Charger’sloadreaches33%oftheInverter/
Charger’s load rating. Charger output falls
gradually from full output at 33% of the
Inverter/Charger’sloadratingtoabout40%
of full output at full load.
Configuration (continued)
B1B2B3B4
B1B2B3B4
Group B DIP Switches
Select AC Sharing—OPTIONAL
Your Inverter/Charger features a high-output battery charger that can draw a significant amount of AC power from your utility source or
generatorwhenchargingatitsmaximumrate.IfyourunitissupplyingitsfullACpowerratingtoitsconnectedheavyelectricalloadsatthe
same time as this high charging occurs, the AC input circuit breaker could trip, resulting in the complete shut off of pass-through utility
power.
To reduce the chance of tripping this breaker, all APS Inverter/Chargers may be set to automatically limit the charger output. This keeps the sum
of the unit’s AC load and charge power within the circuit breaker rating. This charger-limiting function has two settings, allowing you to
reduce the charger’s draw lower and lower, as needed, if the AC input circuit breaker keeps tripping under the normal AC loads of devices you
have connected downline from the unit. The figures show how to set your DIP Switches for charger-limiting.
B1
B2
Set Battery Charging Amps—OPTIONAL
Check the nameplate for your unit’s high-
and low-charging amp options. By setting
on high charging, your batteries will charge
atmaximumspeed.Whensettingonlow
charging, you lengthen the life of your
batteries (especially smaller ones).
Battery Charger Switch Position
LowChargeAmps Up(factorysetting)
HighChargeAmps Down
CAUTION: When switching to the High Charge Amp setting, the user must ensure that the
amp hour capacity of their battery system exceeds the amperage of the High Charge Amp
setting or the batteries may be damaged or degraded.
Select Equalize Battery Charge—OPTIONAL
This DIP Switch is momentarily engaged
to begin the process of equalizing the
charge state of your battery’s cells by time-
limited overcharge of all cells. This can
extend the useful life of certain types of
batteries; consult with your battery’s
manufacturer to determine if your batteries could benefit from this
process.Thechargeequalizationprocessisautomatic;oncestarted,
it can only be stopped by removing the input power.
Setting Procedure
• Moveto“Equalize”(DOWN)positionforthreeseconds.
• Moveto“Reset”(UP)positionandleaveitthere.Thisisthe
factory default setting.
CAUTION: Do not leave DIP switch #B3 in the down position after beginning process. Battery
charge equalization should only be performed in strict accordance with the battery manufacturer’s
instructions and specifications.
Battery Charge Switch Position
Reset Up(factorysetting)
Equalize Down—momentarily
B1B2B3B4
Reset
Equaliz
e
B1B2B3B4
B4
B3
(factory setting)