1.2.7 Battery Voltage (LED 5-8)
LED 5-8 indicate the battery capacity as detailed in the following table:
Battery Voltage LED 5 LED 6 LED 7 LED 8
25% On — — —
50% On On — —
75% On On On —
100% On On On On
1.2.8 Voltage Setting (Switch 1-3)*
Switch ON OFF
DC-to-AC Transfer Delay (Switch 1) 30 sec (Default) 5 sec
Low Battery Alarm (Switch 2) 11.2V 10.9V (Default)
AC Transfer Voltage (Switch 3) 95V 85V (Default)
*Note:
1. Switch 1 is located farthest from the battery temperature port. See diagram on page 3.
2. All switches must be set before the system is turned on.
3. Switch 2 sets the low battery voltage alarm level (at higher voltage, the alarm sounds sooner).
4. Switch 3: Low-level AC-to-DC voltage point. If the AC input voltage decreases to below the setpoint, the inverter will
automatically switch to DC MODE. Please see the table for details.
Nominal Voltage Low Voltage Transfer Point (AC-to-DC) Return Voltage Point (DC-to-AC)
120V
On 95 100
Off 85 90
1.2.9 Search Mode Setting (Switch 4)
Search Mode activates when the unit is operating in inverter mode (battery power) to prevent unnecessary battery discharge
when electrical power is not required. If the inverter is supporting loads that must constantly be powered, turn off switch 4 to
disable Search Mode.
Switch 4 Search Mode Function
ON Enable Inverter only turns on if load > 100W
OFF (Default) Disable
Inverter is always on in the absence of
AC power
1.2.10 Battery Type/Floating Voltage (Switch 5)
Switch 5 Floating Voltage Acceptance Voltage Battery Type
ON (Default) 13.8V 14.5V Absorbed Glass Mat (AGM)
OFF 13.2V 13.8V Wet-Cell
Note: The unit will charge the battery to Acceptance voltage, continue for up to 12 hours, then drop to Floating voltage.