UNIPLAY HMI QUICK CONNECTION GUIDE Quick Start Guides 1
USING UNIPLAY UNIPLAY HMI’s work with the Trio 4xx Motion Coordinator range. Motion Perfect 3 is used to create operator HMI screens which are transferred to the UNIPLAY HMI by the Motion Coordinator at runtime. Trio recommend using a USB powered switch CONFIGURATION RUNNING To allow a laptop PC to be connected to the Motion Coordinator at the same time as the HMI, an Ethernet switch / hub is required. 2 INTRODUCTION REQUIREMENTS UNIPLAY HMI is a whole new way of creating and storing HMI screens.
INSTALLATION 1 The Motion Coordinator default IP address is 192.168.0.250 2 The UNIPLAY panel default IP address is 192.168.0.251 3 The HMI panel must be aware of the Motion Coordinator IP address. If this is not at default use MPv3 Tools->Setup UNIPLAY HMI device screen to store the Motion Coordinator IP address into the panel. 4. Whilst attempting to connect to the Motion Coordinator the panel displays a page: If no HMI page exists, the UNIPLAY panel will display”invalid HMI page”.
CREATING AN HMI PAGE The new blank page will open in the editor: Right mouse click on “Programs” or use Program->New on the menu The components on the left hand column can be dragged and dropped on the page. The top border tools are used to edit and align pages.
The properties of each component can be edited by a menu brought up using a right mouse click: The menu then lets you choose what type of controller data to link to. This can be a program variable, for example in the program “MAINPROG” below, or VR, or other controller data types. LINKING PROPERTIES TO CONTROLLER DATA The properties of each component can be fixed or linked to controller data. To link a component property to controller data click on the small “chain” bitmap alongside each property.
To see the screen run live on the UNIPLAY HMI simply click the green “upload” button: CREATING FURTHER HMI PAGES Further pages are made in the same way as the first page by right-clicking “Programs”. Note how one HMI screen is set to be the “Start-up page”. This is the first page that will be displayed and is highlighted in bold in the program tree. You can select a different page to be the Start-up Page using the right-click menus.
symbol alongside the action type. A further menu level then allows you to set the action such as “Go to page”, “Set variable” or even “Execute command” which will execute a line of BASIC. The BASIC line can include colon “:” separators to allow some multi-line sequences to be executed. SOFTWARE INSTALLATION The UNIPLAY HMI device software runs on the Windows CE operating system installed on the panel. No additional software installation is required to use the UNIPLAY HMI system.
Environmental Considerations • The UNIPLAY are to be used indoors as built in displays. Make sure that the display are installed correctly and that the operating limits are followed. • Do not operate the unit in areas subject to explosion hazards due to flammable gases, vapours or dusts. • The unit should not be installed where large temperature variations and/or high humidity is present. This will cause condensation in the device. • Do not install UNIPLAY in environments where have inflammable gases.
The power conditioning circuitry inside the unit is accomplished by a switching power supply. The peak starting current can be as high as 2A. Fusing Requirements If the display does not come on within 5 seconds of power up, switch off the power. An internal fuse will prevent damage if the polarity of the d.c. power is incorrect. Check wiring to insure proper connections and try to power up again. High Voltage An Internal fuse will prevent damage for over voltage condition however it is not guaranteed. D.
the central star earth point. Ground conductors should be as short and as wide in size as possible. The conductors must always be large enough to carry the maximum short circuit current of the path being considered. Ground conductors should be connected to a tree from a central star earth ground point. This ensures that no ground conductor carries current from any other branch.
DIMENSIONS AND PORTS A B C D E F DIP switch & reset button Fuse Power connector VESA 75mm screw holes Line out SD card slot G H I J K Com1 RS485, Com3 RS485, Com3 RS232 Com1 RS232, Com2 RS232 Ethernet port USB Host port USB Client port R2mm A D 138mm CUTOUT DIMENSIONS B C 192mm 146.35mm 42.55mm 200.
R2mm D A CUTOUT DIMENSIONS 201mm B C 259mm 212.97mm 50mm 270.97mm E F G H I J K UNIPLAY 10 UK | USA | CHINA | INDIA WWW.TRIOMOTION.