User Manual
TMCM-1276 CANopen
®
Firmware Manual • Firmware Version V3.22 | Document Revision V1.00 • 2018-JUN-28
85 / 114
Entry Description
Sub-index Access PDO Mapping Value Range Default Value
0 rw see CiA402-3 SIGNED32 0
Table 270: Entry Description (60FF
h
)
7.2 How to move a Motor in pv Mode
Here is a little example that shows how to get a motor running in pv mode. In this little example we assume
that the module has been reset (and then switched to pre-operational or operational) by NMT commands
before.
•
If you do not have any limit switches connected, first disable the limit switch inputs by writing 3 to
object 2005
h
.
• Select pv mode by writing 3 to object 6060
h
.
• Write 6 to object 6040
h
to switch to READY_TO_SWITCH_ON state.
• Write 7 to object 6040
h
to switch to SWITCHED_ON state.
• Write 15 to object 6040
h
to switch to OPERATION_ENABLED state.
•
Write the desired target speed (e.g. 100000) to object 60FF
h
. The motor now accelerates to that
speed.
• Stop the motor by writing 0 to object 60FF
h
.
©2018 TRINAMIC Motion Control GmbH & Co. KG, Hamburg, Germany
Terms of delivery and rights to technical change reserved.
Download newest version at www.trinamic.com