5 Functional Description
5.1 Typical Application Wiring
Wire the PD42-1070 as shown in the following figures.
• Connect the the power supply to V+ and GND.
• Connect the Step and Direction signals to your motion controller.
• At power up time, the EN input must be low (= driver stage disabled)!
•
Optional: Connect UART to a TTL UART interface with 5V logic levels. To configure your PD42-1070
connect start the TMCL-IDE and use the parameterization tools. For detailed instructions refer to the
PD42-1070-firmware-manual.
Note
The TTL UART interface is not optically isolated. It requires 5V level signals.
Nevertheless, it provides basic ESD and rail-to-rail signal line protection for the
PD42-1070.
Figure 10: Typical application scenario with 5V inputs
5.2 Optically Isolated Inputs with Common Anode Input
The control inputs of the PD42-1070 are optically isolated (not the TTL UART interface). All optocouplers
share one common anode (COMM) input as shown in the figure above.