5  Global Parameters 
GLOBAL PARAMETERS ARE GROUPED INTO 4 BANKS:  
-  bank 0 (global configuration of the module) 
-  bank 1 (user C variables)  
-  bank 2 (user TMCL variables) 
-  bank 3 (interrupt configuration) 
Please use SGP and GGP commands to write and read global parameters. 
5.1  Bank 0 
Parameters with numbers from 64 on configure stuff like the serial address of the module and the RS485 
baud rate. Change these parameters to meet your needs. The best and easiest way to do this is to use the 
appropriate  functions of the TMCL-IDE.  The parameters  with numbers between 64 and 128  are stored  in 
EEPROM only.  
Attention: 
-  An SGP command on such a parameter will always store it permanently and no extra STGP command 
is needed. 
-  Take care when changing these parameters, and use the appropriate functions of the TMCL-IDE to do 
it in an interactive way! 
MEANING OF THE LETTERS IN COLUMN ACCESS 
Access 
Type 
Related 
Command(s) 
Description 
R 
GGP 
Parameter readable 
W 
SGP, AGP 
Parameter writable 
E 
STGP, RSGP 
Parameter automatically restored from EEPROM after reset or power-on. These 
parameters  can  be  stored  permanently  in  EEPROM  using  STGP  command  and 
also explicitly restored (copied back from EEPROM into RAM) using RSGP. 
GLOBAL PARAMETERS (BANK O) 
Number 
Parameter 
Description 
Range 
Access 
64 
EEPROM magic 
Setting this parameter to a different value as 
$E4 will cause re-initialization of the axis and 
global  parameters  (to  factory  defaults)  after 
the  next  power  up.  This  is  useful  in  case  of 
miss-configuration. 
0… 255
RWE 
65 
RS485 baud rate 
0 
9600 baud 
Default 
1 
14400 baud 
2 
19200 baud 
3 
28800 baud 
4 
38400 baud 
5 
57600 baud 
6 
76800 baud  
Not supported by Windows! 
7 
115200 baud 
8 
230400 baud 
9 
250000 baud  
Not supported by Windows! 
10 
500000 baud  
Not supported by Windows! 
11 
1000000 baud  
Not supported by Windows! 
0… 11 
RWE 
66 
Serial address  
The module (target) address for RS485. 
0… 255
RWE 
68 
Serial heartbeat 
Serial heartbeat for the RS485 interface. If this 
time  limit  is  up  and  no  further  command  is 
noticed the motor will be stopped.  
0 – parameter is disabled 
[ms] 
RWE 