PD-1141 TMCL Firmware V1.19 Manual (Rev. 1.01 / 2012-JUL-27)  27 
www.trinamic.com   
3.6.5  SAP (set axis parameter) 
With this command most of the motion control parameters of the module can be specified. The settings 
will be stored in SRAM and therefore are volatile. That is, information will be lost after power off.  
Please use command STAP (store axis parameter) in order to store any setting permanently.  
For a  table with parameters and values which can be used together with this command please refer  to 
chapter 4. 
Internal function: The parameter format is converted ignoring leading zeros (or ones for negative values). 
The parameter is transferred to the correct position in the appropriate device.  
Related commands: GAP, STAP, RSAP, AAP 
Mnemonic: SAP <parameter number>, 0, <value> 
Binary representation: 
INSTRUCTION NO. 
TYPE 
MOT/BANK 
VALUE 
5 
<parameter number> 
0* 
<value> 
 *motor number is always O as only one motor is involved 
Reply in direct mode: 
STATUS 
VALUE 
100 – OK 
(don't care) 
Example: 
Set the absolute maximum current of motor to 200mA 
Mnemonic: SAP 6, 0, 200 
Binary: 
Byte Index 
0 
1 
2 
3 
4 
5 
6 
7 
Function 
Target- 
address 
Instruction 
Number 
Type 
Motor/ 
Bank 
Operand 
Byte3 
Operand 
Byte2 
Operand 
Byte1 
Operand 
Byte0 
Value (hex) 
$01 
$05 
$06 
$00 
$00 
$00 
$00 
$c8 