5.7.37 Request target position reached event 
This command is the  only exception to the  TMCL™ protocol, as it sends two replies: One immediately after 
the command has been executed (like all other commands also), and one additional reply that will be  sent 
when the motor has reached its target position. This instruction can only be used in direct mode (in stand 
alone mode, it is covered by the WAIT command) and hence does not have a mnemonic.  
Internal function: Send an additional reply when the motor has reached its target position  
Mnemonic: --- 
Binary representation: 
INSTRUCTION NO. 
TYPE 
MOT/BANK 
VALUE 
138 
(don’t care) 
(don’t care) 
0* 
 * Motor number 
Reply in direct mode (right after execution of this command): 
Byte Index 
0 
1 
2 
3 
4 
5 
6 
7 
8 
Function 
Target- 
address 
Target- 
address 
Status 
Instruction 
Operand 
Byte3 
Operand 
Byte2 
Operand 
Byte1 
Operand 
Byte0 
Checksum 
Value (hex) 
$02 
$01 
100 
138 
$00 
$00 
$00 
Motor bit 
mask 
<checksum
> 
Additional reply in direct mode (after motors have reached their target positions): 
Byte Index 
0 
1 
2 
3 
4 
5 
6 
7 
8 
Function 
Target- 
address 
Target- 
address 
Status 
Instruction 
Operand 
Byte3 
Operand 
Byte2 
Operand 
Byte1 
Operand 
Byte0 
Checksum 
Value (hex) 
$02 
$01 
128 
138 
$00 
$00 
$00 
Motor bit 
mask 
<checksum
> 