Installation Guide for SecureMesh
®
WAN Extender 2 - PL-0072A
28. Also ensure that the surge module’s four panel fasteners are secure and fully
threaded.
Setting the configuration
Each XTEN-2000 is shipped from the factory with its configuration set to factory default
values. Prior to deployment and installation, certain operating parameters may need to
be configured. For details on parameters and setting the configuration, see the
following applications and manuals:
l Administrator Guide for SecureMesh WAN and NEMS
l Command Line Interface Reference
The XTEN-2000 can be configured using a Telnet connection either through the RJ45
port, or through a wireless link via the internal WiFi radio. The following section outlines
the Telnet connection through the RJ45 port. The basic Telnet setup is shown in Figure
21. Use the Cat5 or Cat6 Ethernet cables to connect the PSE to the XTEN-2000 and
the test computer.
1. Plug one Ethernet cable into the data port on the PSE. Plug the other end of
the cable into the test computer's wired network port.
2. Then plug a second Ethernet cable into the data/power port on the PSE. Plug
the other end of the cable into the RJ45 port on the XTEN-2000.
3. Apply input power to the PSE, and wait approximately 120 seconds for the
XTEN-2000 to fully boot before attempting to connect via Telnet.