User Manual

SkyPilot SkyAccess DualBand Installation 46
Grounding Checklist
When grounding a SkyPilot device, use the following checklist to
confirm that your installation is adequately protected from power
surges and lightning.
Connect a ground wire from the SkyPilot device to a ground system
on the building or tower.
Use shielded CAT5 cabling and connect the drain wire of the shield
to ground at the SkyPilot device. (Leave the other end of the drain
wire unconnected.)
Use the proper size down lead to connect a SkyPilot device on a
roof or tower to the ground system of indoor equipment.
Verify that all points of the ground system are tied together with
less than 5 ohms resistance between any two points.
Run the CAT5 cable inside the tower structure, tying the cable to
the tower leg at every 4 feet of length. For increased protection,
run the CAT5 cable through metallic conduit installed on the tower.
Bleed off any static charge by installing a streamer-delaying, static-
dissipation array above the SkyPilot device.
Install all lightning and surge protection devices in accordance with
UL 96A installation requirements for lightning protection systems
and the NFPA 780 standard for lightning protection.