User Manual
Applications
12
Boiler (180 ºF-160 ºF) Radiant (100 ºF-120 ºF)
Chart 3: Radiant/Snowmelt Application Sizing
The sizing given in Chart 3 includes only a general
overview of sizing applications available. For addi-
tional or more detailed sizing parameters contact
your local Triangle Tube Distributor or Triangle
Tube’s Engineering Department.
The sizing given in Chart 3 does not account for any
glycol solution used in a snowmelt application.
NOTICE
NOTICE
Model
Btu/Hr
Supplied
Boiler
GPM
Pressure Drop
PSIBoiler
Radiant/
Snowmelt
GPM
Pressure Drop
PSIRadiant/
Snowmelt
TTP1-14E 25,000 2.6 0.5 2.5 0.4
TTP1-14E 30,000 3.1 0.8 3.0 0.6
TTP1-14E 35,000 3.6 1.1 3.5 0.9
TTP1-14E 40,000 4.1 1.4 4.0 1.1
TTP1-14E 45,000 4.6 1.8 4.5 1.4
TTP1-14E 50,000 5.2 2.3 5.0 1.7
TTP1-14E 55,000 5.7 2.8 5.5 2.1
TTP1-14E 60,000 6.2 3.4 6.0 2.5
TTP1-14E 65,000 6.7 4.0 6.5 2.9
TTP1-14E 70,000 7.2 4.6 7.0 3.4
TTP3-20 100,000 10.3 1.6 10.1 1.3
TTP3-20 125,000 12.9 2.6 12.6 2.1
TTP3-20 150,000 15.5 3.8 15.2 3.0
TTP3-20 175,000 18.8 5.2 17.7 4.1
TTP3-20 200,000 20.6 6.9 20.2 5.5
TTP3-20 225,000 23.2 8.8 22.7 7.0