Brazed Plate Heat Exchangers TTP’s Series ® PRODUCT INFORMATION- APPLICATIONS INSTALLATION - MAINTENANCE GUIDE WARNING Before proceeding with installation and operation, read entire manual carefully. Failure to do so can cause injury or property damage. NOTICE Date: 10/2/13 TTP heat exchangers are not compatible with ammonia (NH3) When receiving TTP’s, any claims for damage or shortage in shipment must be filed immediately against the transportation company by the consignee.
Table of Contents Product and Safety Information. . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1 General Product Information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2 Operating and Code Restrictions . . . . . . . . . . . . . . . . . . . . . . . . . . . 3 General Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-6 Maintenance and Cleaning . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7 Domestic Water Applications.
Product and Safety Information Following terms are used throughout this manual to bring attention to the presence of potential hazards or to important information concerning the product. CAUTION DANGER Indicates a potentially hazardous situation which, if ignored, may result in minor injury or property damage. WARNING Indicates special instructions on installation, operation, or maintenance, which are important to equipment but not related to personal injury hazards.
general Product Information HIgH EffICIEnCy aPPlICaTIonS The design of the plates creates two separate channels for a true counter current flow movement. This complex channel system results in high turbulence and high heat transfer. TTP Braze Plate Heat Exchangers are suitable for a variety of single-phase fluid-to-fluid and two-phase refrigerant to fluid applications.
operation and Code restrictions ProduCT aPProvalS WaTEr / fluId QualITy rESTrICTIonS - • - Triangle Tube’s TTP Braze Plate Heat Exchangers are UL approved. • ASME is available as an option. • CodE CoMPlIanCE & rESTrICTIonS • • • All piping and installations must conform with the instructions listed in this manual and where applicable: - • Local, state, provincial and national codes.
general Installation MounTIng guIdElInES gEnEral InSTallaTIon rEQuIrEMEnTS - Ensure all plumbing / piping meets or exceeds all local, state or national codes. - Install unions for easy removal of the braze plate heat exchanger. It is recommended to use dielectric unions or couplings to protect fittings from corrosion when connecting dissimilar materials such as copper and galvanized iron pipe.
general Installation fig.1: recommended Methods of Mounting fig.3: Multiple Series arrangement Red label SoldErIng and WEldIng ConnECTIonS Soldering Procedures: fig.2: recommended Mounting Position Recommended solder material: 30 - 55% silver alloy gEnEral PIPIng arrangEMEnTS - MulTIPlE HEaT ExCHangErS Recommended flux material: Black flux for silver soldering 1. Degrease and clean the soldering surfaces on the piping and the heat exchanger connections. Multiple Heat Exchangers in Series - - 2.
general Installation WARNING WARNING do not braze the heat exchanger in a horizontal or flat position. Solder material may fall into the heat exchanger or piping connection, creating a blockage within the distribution channels . direct the flame away from the heat exchanger do not heat the welding area higher than 1200ºf. damage to the heat exchanger brazing material could occur. fig. 5: Welded Connection THrEadEd ConnECTIonS fig. 4: Solder Connection General Guidelines • WEldIng ProCEdurES 1.
Maintenance and Cleaning WARNING gEnEral guIdElInES for ClEanIng • • • • To prevent damage to the heat exchanger and refrigerant components, do not chemically clean the refrigerant circuit of the heat exchanger. A 5% solution of Phosphoric Acid or Oxalic Acid is recommended as a cleaning solution. Other types of cleaning solutions such as ice making machine de-scaler are available and may be used, check the manufacturer’s instructions for compatability.
applicatons doMESTIC WaTEr aPPlICaTIonS • Typically the fluid circuit with the highest temperature and/or pressure should be connected to the left side connections as indicated with the colored label. • Primary Supply The circuit flows should be piped in a counterflow arrangement. • Domestic Inlet Primary Return On instantenous water heating applications (applications without any storage tank) a flow switch must be used to prevent overheating of the heat exchanger.
applications fig. 9: Example of TTP heat exchanger providing instantaneous dHW fig.
applications NOTICE Chart 2: domestic application Sizing Boiler Water Supply: 180 ºF, Domestic Inlet Temp.: 50 ºF The sizing data in Chart 2 includes only a general overview of sizing applications available. for additional or more detailed sizing parameters contact your local Triangle Tube distributor or Triangle Tube’s Engineering department.
applications radIanT and SnoW MElT aPPlICaTIonS • • • • Typically the fluid circuit with the highest temperature and/or pressure should be connected to the left side connections as indicated with the colored label. The circuit flows should be piped in a counterflow arrangement. Use antifreeze specifically intended for hydronic heating systems. Inhibited propylene glycol is recommended. Typical boiler water to glycol blend is 10% to 40% depending on location and weather conditions. fig.
applications Chart 3: radiant/Snowmelt application Sizing Model TTP1-14E TTP1-14E TTP1-14E TTP1-14E TTP1-14E TTP1-14E TTP1-14E TTP1-14E TTP1-14E TTP1-14E Btu/Hr Supplied Boiler gPM 30,000 3.1 25,000 35,000 40,000 45,000 50,000 55,000 60,000 65,000 70,000 2.6 4.1 TTP3-20 TTP3-20 TTP3-20 175,000 200,000 225,000 0.9 3.4 6.7 4.0 7.2 15.5 3.5 2.8 6.2 150,000 1.1 2.3 5.7 TTP3-20 0.4 1.8 5.2 10.3 125,000 2.5 1.4 4.6 100,000 0.5 0.8 3.
applications STEaM To WaTEr aPPlICaTIonS • • • • rEfrIgEranT (CondEnSEr / EvaPoraTor) aPPlICaTIonS Ensure the braze plate heat exchanger is mounted vertically to allow gravity drainage of the condensate. Condenser applications • The installer should use “Good Steam Practices” which include a steam trap below the unit and vacuum breakers. • The steam circuit must enter the heat exchanger’s top connection, with the condensate leaving the heat exchanger through the bottom connection.
Technical data Fig.
Product Selection With our computer program we will select the optimum heat exchanger for your particular applications. Please fax this selection sheet back to our Engineering Department. Date: Brazed Plate Heat Exchanger Submit this information to Triangle Tube for computerized sizing assistance. Our program will select the optimum heat exchanger for your particular application. Application Parameters Fax: (856) 228 3584 - Tel: (856) 228 8881 Media Fax: Job Ref.
PrESTIgE Condensing Wall Mounted Boiler - - - - - - - 95% AFUE - Enegy Star Certified Fully modulating Natural gas or propane Stainless Steel Construction Direct vent with standard schedule 40 PVC Outdoor Reset Low Nox SMarT Series Indirect fired Water Heaters - - - - - - Exclusive “tank-in-tank” design Stainless steel construction Available in 7 sizes Limited LIFETIME residential warranty 6 year limited commercial warranty Self cleaning/self descaling design Maxi-flo Pool and Spa