Installation - Piping
When the water supply pressure is higher than
70 psig, it is recommended to install a pressure
reducing  valve  on  cold  water  supply  line  to
prevent water loss through T&Prelief valve.
If  water  heater  will  replace  tankless  coil  in
boiler, disconnect piping to coil. Allow water
to drain from coil. Do not plug tankless coil.
Plugging tankless coil inlet and outlet will
result in severe personal injury, death, or
substantial property damage.
Thermostatic Mixing Valve
It is recommended to install an optional mixing
valve on the domestic hot water outlet.
Mixing valve should comply with ASSE 1017
Recirculation Piping
T&P relief  valve  must  be  installed  in  run
(straight through leg) of tee located at domestic
hot water outlet of water heater.
It isrecommendedthat the recirculation dip tube
be installed inauxiliary connection using a close
nipple assembly asshown Fig. 3A, page 9.See
Chart  1  page 6 for diameter and length  of  dip
tube.
Astainless steel or bronze circulator is recom-
mended
Install automatic mixing valve either at the hot
water outlet of water heater or each hot water
faucet.
Multiple Water Heater Systems
Parallel Pipe Recirculation Systems - Manifold
recirculation return to all water heaters.
Series Piped Systems - Piped return to the lead-
ing (cold water inlet) water heater.
Install automatic mixing valve either at the hot
water outlet of water heater or each hot water
faucet.
Failure to install automatic mixing valve
where recommended will result in severe
personal injury or death.
Boiler Piping
If plastic pipe is used for boiler water piping, it
must have a maximum oxygen diffusion rate of
0.1  mg/liter-day  for  boiler  and  water  heater
protection.
The Smart IDWH must be installed on a
closed type hydronic system. Failure to pro-
vide such a system will result in premature
failure of the outer tank and annulment of
warranty.
Boiler  water  (including  additives)  must  be
practically non-toxic, having toxicity rating or
class  of 1,  as  listed  in  Clinical Toxicology  of
Commercial Products.
If  antifreeze  is  used  in  boiler  system,  local
codes  may  require  a  backflow  preventer  on
cold water supply line. Use antifreeze specifi-
cally  intended  for  hydronic  heating  systems.
Inhibited propylene glycol is recommended at
a maximum 50/50 mixture.
Do not use automotive, ethylene glycol or
petroleum-based antifreeze. Do not use any
undiluted antifreeze. This can cause severe
personal injury, death or substantial property
damage.