Manual

Installation - Piping
5
Do not install any valve between T&P relief
valve and tank connection or on T&P relief
valve discharge piping. Do not plug T&P
relief valve or discharge piping. Improper
placement and piping of T&P relief valve
can cause severe personal injury, death or
substantial property damage.
Drain Valve
Drain valve and fittings are supplied by others.
Standard Installation
Install a tee connection at the domestic cold
water inlet (Fig. 1 and 2 page 8).
Pipe the drain piping with drain valve from
the tee connection to:
- a suitable place for disposal
or
- terminate within 12” of the floor
Commonwealth of Massachusetts Installation
Thread a 3/4” close nipple onto the
Auxiliary  connection  and  insert  an  open-
end dip tube into the Auxiliary connection
on top of water heater. As shown in Fig. 3A
page 9.
Install  a  3/4” NPT elbow  to  the Auxiliary
connection, see Fig. 3B page 9
Pipe the drain piping with drain valve from
the elbow connection to:
- a suitable place for disposal
or
- terminate within 12” of the floor 
Automatic Air Vent
1. Remove plastic shipping cap from 1/2” NPT
pipe fitting on top center of water heater.
2. Install1/2x1/8reducerbushing providedwith
water heater, using suitable pipe dope or tape.
3. Install automaticair ventprovided with water
heater, using suitable pipe dope or tape.
4. Unscrewventcaponairventonefullturn.Leave
cap unscrewedoneturn fornormal venting.
Thermal Expansion
If  a  backflow  preventer,  check  valve  or  pressure
reducing valve is piped on cold water supplypiping
of  water heater,  install  an  expansion  tank  on  cold
water supply lineto preventnormal thermal expan-
sion from repeatedly forcing open T&P relief valve.
T&P relief valve is not intended for constant
duty, such as relief of pressure due to
repeated normal system expansion. Correct
this condition by installing a properly sized
expansion tank in domestic water system.
Refer to expansion tank manufacturer’s
installation instructions for proper sizing.
Water Hammer
Dishwashers, clothes washers and fast-closing pos-
itive shut-off valves incorporated in the system all
contribute to creating water shock. Install a water
hammer  arrester  to  prevent  damage  to  pipes  and
appliances.  See device manufacturers instructions
for application and installation.
Water hammering within the domestic pip-
ing system can cause premature failure of
the inner tank of the water heater. This type
of failure is NOT covered under warranty.
WARNING
CAUTION
NOTICE