Manual

Pre-Installation
2
Codes Compliance
Water  heater  installation  must  conform  with  the
instructions in this manual and where applicable:
local, state, provincial, and national codes,
laws, regulations and ordinances.
in Canada - CAN / CGA B149.1 or B149.2
Installation Code.
SMART water  heaters  are exempt  from  ASME
Section  VIII,  Division  1  Code  construction per
Interpretation VIII-86-136. Check with local codes
for applicability.
SMART Series water heaters will absorb
less than 200,000 BTU/hr when domestic
water outlet temperature is 210ºF and boiler
water supply temperature is 240ºF. Listed
outputs are based on ASME Section VIII
Interpretation VIII-1-86-136.
Where  recommendations  in  this  manual  differ
from local, or national codes, the local or national
codes take precedence.
Codes Restrictions
Single  wall  heat  exchanger  in  the  SMART water
heater complies with National Standard Plumbing
Code, provided that:
boiler water (including additives) is practically
non-toxic, having toxicity rating or class of 1,
as listed in Clinical Toxicology of Commercial
Products, and
boiler  water  pressure  is  limited  to  maximum
30 psig by approved relief valve.
Single wall heat exchangers are permitted under the
Uniform Plumbing code - Paragraph L3.2. and L3.3
if they satisfy allof the following requirements.
1. Theheattransfer medium is potable wateror
contains  only substances  which  are recog-
nized  as  safe  by  the U.S.  Food  and  Drug
Administration.
2. The pressure of the heat transfer medium is
maintained less than the normal  minimum
operating pressure ofthepotable watersystem
Exception: Steam  complying  with  sec-
tion #1 above.
3. The equipment is permanently  labeled  to
indicate  that only  additives recognized  as
safe  by  the  FDA shall  be  used  in the heat
transfer medium.
Other  heat  exchanger  designs  may  be  permitted
where approved by theAdministrativeAuthority.
Operating Restrictions
Maximum domestic hot water temperature
is  194ºF  for  commercial  applications  and
140ºF for residential applications.
Maximum boiler water temperature is
210ºF.
Maximum working pressure for inner
(domestic water) tank is 150 psig.
Maximum working pressure for outer
(boiler water) tank is 45 psig.
pH  and  chloride  limits  for  water  heaters
are:
- chloride, less than 150 mg/l (ppm)
- pH value min. 6 - max. 8
Any water conditioning system must be
installed and maintained in accordance with
manufacturer’s specifications.
Do not install the water heater on any appli-
cation if the boiler piping contains non-oxy-
gen barrier tubing or if the boiler piping is
considered an “open system”. Exposing the
outer tank of the water heater to oxygen
contamination will lead to premature tank
failure and denial of the warranty.
NOTICE
NOTICE
NOTICE