Smart 40 Indirect Water Heater Manual

29
661A0300 - Rev B
Performances
MODEL
Boiler Heating
C
apacity MBH
Peak Flow
g
al./ 10 min.
1st Hour Flow
G
al./Hour
Continuous Flow
G
al./ Hour
Circulator
M
in. GPM
SMART 30 87 40 140 115 5
SMART 40 112 50 180 150 7
SMART 50 140 65 220 185 8
SMART 60 270 100 410 360 16
SMART 80 300 125 460 400 18
SMART 100 337 150 525 450 25
SMART 120 420 190 650 560 28
Conditions:
- 50ºF Domestic cold water inlet temperature
- 140ºF Domestic hot water outlet temperature
- 200ºF Boiler water supply temperature
MODEL
Boiler Heating
Capacity MBH
Peak Flow
gal./ 10 min.
1st Hour Flow
Gal./Hour
Continuous Flow
Gal./ Hour
Circulator
Min. GPM
SMART 30 115 60 235 210 8
SMART 40 130 70 270 240 9
SMART 50 180 95 370 330 12
SMART 60 320 145 635 590 21
SMART 80 340 165 690 630 24
SMART 100 380 185 775 700 26
SMART 120 445 235 915 820 30
Conditions:
- 50ºF Domestic cold water inlet temperature
- 115ºF Domestic hot water outlet temperature
- 200ºF Boiler water supply temperature