Smart 40 Indirect Water Heater Manual

Installation - Piping
Recommended for applications in which there is a
large water consumption in short period of time.
A maximum of 3 water heaters may be piped in series.
Utilize the lead (hot water outlet) SMART tank ther-
mostat to control system temperature.
Install automatic mixing valve at either the hot water
outlet of the water heater system or at each hot water
fixture.
Each tank should be piped with a drain as shown in
Fig. 1.
13
Multiple SMART Series Water Heater
System Domestic Piping - Parallel
Multiple SMART Series Water Heater
System Domestic Piping - Series
Recommended for most applications.
Any one water heater tank thermostat may be
utilized to control system temperature.
Install automatic mixing valve at either the hot
water outlet of the water heater system or at
each hot water fixture.
Each tank should be piped with a drain as
shown in Fig. 1.
Fig. 10:
Fig. 11:
661A0300 - Rev B