Smart manual_Smart manual 10/29/14 10:00 AM Page 1 Indirect Fired Water Heater LI Technical Specifications Installation and Maintenance Guide STED WARNING IMPORTANT • • • • • • Date Revised 10/29/14 Before proceeding with installation and operation, read entire manual carefully. Failure to do so can cause injury or property damage. When receiving SMART Water Heaters, any claims for damage or shortage in shipment must be filed immediately against the transportation company by the consignee.
Smart manual_Smart manual 10/29/14 10:00 AM Page 2 Table of Contents Product & Safety Information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1 Pre-Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2-3 Installation - Piping Temperature & Pressure (T&P) Relief Valve . . . . . . . . . . . . . . . . . .4-5 Drain Valve . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .5 Manual Air Vent . . . . . .
Smart manual_Smart manual 10/29/14 10:00 AM Page 3 Product & Safety Information Definitions DANGER Following terms are used to bring attention to the presence of various risk levels, or to important information concerning product life. Hot Water Can Scald! • Water temperatures over 125ºF can cause severe burns instantly or death from scalding. • Never leave them unattended in or near shower, bathtub or sink.
Smart manual_Smart manual 10/29/14 10:00 AM Page 4 Pre-Installation Codes Compliance 2. The pressure of the heat transfer medium is maintained less than the normal minimum operating pressure of the potable water system Water heater installation must conform with the instructions in this manual and where applicable: • • Exception: Steam complying with section #1 above. local, state, provincial, and national codes, laws, regulations and ordinances. 3.
Smart manual_Smart manual 10/29/14 10:00 AM Page 5 Pre-Installation Recommended Clearances NOTICE • Any water conditioning system must be installed and maintained in accordance with manufacturer’s specifications. • • NOTICE Do not install the water heater on any application if the boiler piping contains non-oxygen barrier tubing or if the boiler piping is considered an “open system”.
Smart manual_Smart manual 10/29/14 10:00 AM Page 6 Installation - Piping Temperature & Pressure (T&P) Relief Valve Standard Installation • Install T&P relief valve in the Auxiliary connection located behind the air vent on the top of the water heater (Figure 1 page 8).
Smart manual_Smart manual 10/29/14 10:00 AM Page 7 Installation - Piping Thermal Expansion WARNING If a backflow preventer, check valve or pressure reducing valve is piped on cold water supply piping of water heater, install an expansion tank on cold water supply line to prevent normal thermal expansion from repeatedly forcing open T&P relief valve. Do not install any valve between T&P relief valve and tank connection or on T&P relief valve discharge piping.
Smart manual_Smart manual 10/29/14 10:00 AM Page 8 Installation - Piping General Piping • • For domestic water piping diagrams, see pages 8 through 10. See pages 11 through 14 for: - Boiler water piping. - Multiple water heater domestic and boiler piping. • See Chart 1 for domestic and boiler piping connection sizes . • The supplied sealant is suitable for potable water systems. Use only the supplied sealant on all Smart fittings/joints.
Smart manual_Smart manual 10/29/14 10:00 AM Page 9 Installation - Piping Thermostatic Mixing Valve • NOTICE It is recommended to install an optional mixing valve on the domestic hot water outlet. • Mixing valve should comply with ASSE 1017 • T&P relief valve must be installed in run (straight through leg) of tee located at domestic hot water outlet of water heater.
Smart manual_Smart manual 10/29/14 10:00 AM Page 10 Installation - Piping 12" min. Heat Trap Loop (Optional) 12" min. Heat Trap Loop (Optional) M 1 10 H 5 C 1 5 4 Cold Water Inlet 1 6 8 7 Fig. 1: Standard Installation Domestic Piping SMART Series Recirculating Loop 3 2 1 12" min. Heat Trap Loop (Optional) 5 4 1 7 5 6 1 Cold Water Inlet 8 12" min. Heat Trap Loop (Optional) 9 Fig. 2: Standard Installation Domestic Piping with Recirculation SMART Series 1. 2. 3. 4. 5. 6.
Smart manual_Smart manual 10/29/14 10:00 AM Page 11 Installation - Piping Recirculating Loop 12" min. Heat Trap Loop (Optional) 3 2 5 4 1 5 1 7 6 1 Cold Water Inlet 8 12" min. Heat Trap Loop (Optional) Fig. 3: 1. 2. 3. 4. 5. Optional Installation Domestic Piping with Recirculation SMART Series 6. Backflow preventer or pressure reducing valve(*) 7. Drain valve 8.
Smart manual_Smart manual 10/29/14 10:00 AM Page 12 Installation - Piping Fig. 4: Drain Tube AssemblyCommonwealth of Massachusetts 12" min. Heat Trap Loop (Optional) 12" min. Heat Trap Loop (Optional) M 1 10 C 4 H 9 5 5 6 7 1 Cold Water Inlet 8 11 Fig. 5: 1. 4. 5. 6. 7. Commonwealth of Massachusetts Domestic Piping SMART Series Shut-off valves T&P relief valve Unions Backflow preventer or pressure reducing valve (*) Drain valve 661A0300 - Rev B 8. Thermal expansion tank (potable) 9.
Smart manual_Smart manual 10/29/14 10:00 AM Page 13 Installation -Piping 1 3- Port Priority Valve 2 6 3 5 Cold water inlet 1 4 1 Fig. 6: SMART System Piping with 3-Port Zone Valve (Domestic Priority) 2-Port Priority Valve (normally open) 6 3 2 5 2-Port Priority Valve (normally close) Cold water inlet 1 4 1 Fig. 7: SMART System Piping with 2-Port Zone Valves (Domestic Priority) 4. Drain valve 5. Feed valve 6. Air separator 1. Shut-off valves 2. Circulator 3.
Smart manual_Smart manual 10/29/14 10:00 AM Page 14 Installation - Piping Fig. 8: SMART System Piping with Zone Valves (Non Domestic Priority) Fig. 9: SMART System Piping with Zone Circulators 1. 2. 3. 4. Shut-off valves Circulator Flow check valve Expansion tank 661A0300 - Rev B 5. Drain valve 6. Feed valve 7.
Smart manual_Smart manual 10/29/14 10:00 AM Page 15 Installation - Piping Fig. 10: Multiple SMART Series Water Heater System Domestic Piping - Parallel • • • • Fig. 11: Multiple SMART Series Water Heater System Domestic Piping - Series • • • • 13 • Recommended for most applications. Any one water heater tank thermostat may be utilized to control system temperature. Install automatic mixing valve at either the hot water outlet of the water heater system or at each hot water fixture.
Smart manual_Smart manual 10/29/14 10:00 AM Page 16 Installation - Piping Fig. 12: Multiple SMART Series Water Heater System Boiler Piping Reverse Return Balanced Flow Fig. 13: Multiple SMART Series Water Heater System Boiler Piping - Manifold 1. 2. 3. 4. Shut-off valves Circulator Flow check valve Expansion tank 661A0300 - Rev B 5. Drain valve 6. Feed valve 7.
Smart manual_Smart manual 10/29/14 10:00 AM Page 17 Installation - Wiring Wiring Requirements WARNING Electrical shock hazard can cause severe personal injury, death or substantial property damage. Disconnect power before installing and/or servicing. 1. All wiring must be a minimum of 18 gauge and installed in accordance with: • • U.S.A. - National Electrical Code and any other national, state or local code requirements having jurisdiction. Canada - C.S.A. C22.
Smart manual_Smart manual 10/29/14 10:00 AM Page 18 Installation - Wiring Fig. 15: Typical 3-wire Zone Valve Zoning, with Domestic Priority Fig. 14: Typical 4-wire Zone Valve Zoning, with Domestic Priority Transformer (Power) H 120 N V.A.C. High Voltage Transformer (Power) H 120 N V.A.C. High Voltage 24 V.A.C. 24 V.A.C.
Smart manual_Smart manual 10/29/14 10:00 AM Page 19 Installation - Wiring Fig. 16: Typical 4-wire Zone Valve Zoning, without Domestic Priority Transformer (Power) Fig. 17: Typical 3-wire Zone Valve Zoning, without Domestic Priority H 120 N V.A.C. High Voltage Transformer (Power) H 120 N V.A.C. High Voltage 24 V.A.C. 24 V.A.C.
Smart manual_Smart manual 10/29/14 10:00 AM Page 20 Installation - Wiring Fig. 18: Typical Circulator Zoning with Domestic Priority Honeywell R845A Relay 120 H Fig.
Smart manual_Smart manual 10/29/14 10:00 AM Page 21 Installation - Wiring Fig. 20: Priority Zone Circulator Wiring Honeywell R845A Circulator Relay Note: Maximum of 4 total circulator zone when wiring 1 zone for priority.
Smart manual_Smart manual 10/29/14 10:00 AM Page 22 Water Heater Start-Up Filling the Inner (Domestic Water) Tank • • 5. When tank is full, and air stops escaping, close the manual air vent. CAUTION 6. If antifreeze is used in boiler water, check concentration. Boiler water (including additives) must be practically non-toxic, having toxicity rating or class of 1, as listed in Clinical Toxicology of Commercial Products.
Smart manual_Smart manual 10/29/14 10:00 AM Page 23 Water Heater Start-Up General Notes DANGER • HOT WATER CAN SCALD! • • • • • Water temperatures over 125ºF can cause severe burns instantly, or death from scalds. Feel water before bathing or showering. • Consumer Product Safety Commission and some states recommend temperatures settings of 130ºF or less. Setting thermostat higher than 130ºF will increase risk of scald injury and cause severe personal injury or death.
Smart manual_Smart manual 10/29/14 10:00 AM Page 24 Water Heater Start-up Adjusting the Water Heater Thermostat Water heater thermostat is factory set to its lowest temperature. This may or may not be suitable for your needs. Turn thermostat knob clockwise to increase water temperature. Turn thermostat knob counter-clockwise to decrease water temperature. • • Check water temperature at a hot water faucet immediately after first heating cycle.
Smart manual_Smart manual 10/29/14 10:00 AM Page 25 Water Heater Maintenance Maintenance Schedule Annual service by qualified service technician should include the following: Any procedure required by local codes. Check air vent operation. Verify system pressure. Manual air venting procedure may require adding water to bring system up to pressure, typically 12 psig. Manually operate T&P relief valve at least once a year. This will release some hot water.
Smart manual_Smart manual 10/29/14 10:00 AM Page 26 Water Heater Maintenance NOTICE WARNING Do not use automotive, ethylene glycol or petroleum-based antifreeze. Do not use any undiluted antifreeze. This can cause severe personal injury, death or substantial property damage. Prior to draining the inner tank, ensure the following is completed: 1. The snap-set wiring connection at the water heater is disconnected. 2. The DHW system supply isolation valve is closed. WARNING 3.
Smart manual_Smart manual 10/29/14 10:00 AM Page 27 Water Heater Maintenance 5. Apply compressed air at a maximum regulated pressure of 40 psig. 6. When draining is complete, remove the air hose and fittings needed to connect the air hose. Draining Outer (Boiler Water) Tank 1. Disconnect snap set wiring connection at water heater. 2. Close boiler water isolation valves between boiler and water heater. 3. Connect hose to boiler water drain valve at water heater. Open and drain water to a safe place.
Smart manual_Smart manual 10/29/14 10:00 AM Page 28 Replacement Parts SMART Series Item 1 2 3 4 5 Part # P3KITAV02 P3KITTH01 P3KITTH03 P3KITBTM02 P3KITBTM03 P3KITBTM04 P3KITTOP02 P3KITTOP03 P3KITTOP04 P3DW05 P3DW01 P3DW02 P3DW03 P3DW04 6 7 (Not shown) 8 9 10 661A0300 - Rev B P3WKITDT01 P3WKITDT02 P3WKITDT03 P3WKITDT04 P3WKITDT08 P3WKITDT09 P3WKITDT01 P3WKITDT02 P3WKITDT02 P3WKITDT01 P3WKITDT08 (cut to length) P3KITWRS01 P3KNB02 P3CVR04 Models All All All SMART 30, 40, 50 60 SMART 80, 100 SMART 120
Smart manual_Smart manual 10/29/14 10:00 AM Page 29 Replacement Parts 6 4 Thermostat Cover Plate Assembly 5 Located Below Thermostat Cover Plate Assembly 3 SMART 2 8 9 10 2 Thermostat Cover Plate Assembly 27 661A0300 - Rev B
Smart manual_Smart manual 10/29/14 10:00 AM Page 30 Water Heater Specifications Auxiliary Cold Water Inlet Hot Water Outlet Boiler Return Air Vent C Cold Water Inlet Hot Water Outlet A Thermostat & Cover Plate F B Auxiliary Connection Boiler Supply E Top View 661A0300 - Rev B D Rear View 28
Smart manual_Smart manual 10/29/14 10:00 AM Page 31 Performances MODEL Boiler Heating Capacity MBH Peak Flow gal./ 10 min. SMART 40 112 50 SMART 30 87 SMART 50 140 SMART 80 300 SMART 60 SMART 100 SMART 120 Conditions: 40 100 337 150 Peak Flow gal./ 10 min.
Smart manual_Smart manual 10/29/14 10:00 AM Page 32 Additional quality water heating equipment available from: Triangle Tube-ACV Prestige Condensing Wall Mounted Boiler - 95% AFUE - Energy Star Fully modulating Natural gas or propane Stainless Steel Contruction Direct vent PVC, CPVC, PP and SS Outdoor Reset Low NOx Challenger Solo - - Up to 94% AFUE Fully modulating Natural gas or propane Combination copper water tube/aluminum block heat exchanger Direct vent, PVC, CPVC, PP and SS Outdoor reset Low N