Install Instructions

Phase III
®
27
Model Boiler Heating Peak Flow 1st Hour Flow Continuous Flow Circulator
Capacity MBH Gal./10 min. Gal./Hour Gal./Hour Min. GPM
TR-20 80 35 125 110 5
TR-30 87 45 140 115 6
TR-36 118 55 190 160 8
TR-45 137 70 220 185 9
TR-60 270 110 410 360 18
TR-80 337 135 510 450 22
TR-100 375 160 575 500 25
TR-120 420 190 650 560 28
Model Boiler Heating Peak Flow 1st Hour Flow Continuous Flow Circulator
Capacity MBH Gal./10 min. Gal./Hour Gal./Hour Min. GPM
SMART 20 70 35 110 95 5
SMART 30 76 40 125 100 5
SMART 40 106 50 170 140 7
SMART 50 121 65 200 160 8
SMART 60 243 100 370 325 16
SMART 80 285 120 435 380 18
SMART 100 337 150 525 450 25
Conditions: 50º F Domestic Cold Water Inlet Temperature
140ºF Domestic Hot water Outlet Temperature
200ºF Boiler Water Supply Temperature
Performances
Model Boiler Heating Peak Flow 1st Hour Flow Continuous Flow Circulator
Capacity MBH Gal./10 min. Gal./Hour Gal./Hour Min. GPM
TR-20 105 50 210 190 7
TR-30 120 60 245 220 8
TR-36 145 75 300 270 10
TR-45 190 95 390 350 13
TR-60 335 150 665 620 22
TR-80 365 175 730 670 24
TR-100 400 200 825 750 28
TR-120 445 235 915 820 30
Model Boiler Heating Peak Flow 1st Hour Flow Continuous Flow Circulator
Capacity MBH Gal./10 min. Gal./Hour Gal./Hour Min. GPM
SMART 20 95 50 195 175 6
SMART 30 115 60 235 210 8
SMART 40 130 70 270 240 9
SMART 50 180 95 370 330 12
SMART 60 320 145 635 590 21
SMART 80 340 165 690 630 24
SMART 100 380 185 775 700 26
Conditions: 50º F Domestic Cold Water Inlet Temperature
115ºF Domestic Hot water Outlet Temperature
200ºF Boiler Water Supply Temperature