Install Instructions
8
PRESTIGE IGNITION KIT - INSTALLATION INSTRUCTIONS
PRESTIGE TriMax Control
and/or Display Module Replacement
6
Table 1: TriMax Settings
Revised Date: 1/14/14
2011-55 Prestige_TriMax Control &/or Display Module Repl
DOMESTIC SETTING FACTORY DEFAULT MINIMUM SETTING MAXIMUM SETTING
EXISTING SETTING
DHW Operation Enabled
Demand Switch
Boiler DHW Setpoint 186°F [86°C] 96°F [35°C] 188°F [87°C]
DHW Storage Setpoint 140°F [60°C] 68°F [20°C] 150°F [65°C]
DHW On Differential 6°F [3°C] 4°F [2°C] 18°F [10°C]
DHW Storage Adder 46°F [25°C] 0°F [0°C] 54°F [30°C]
DHW Post Pump Time 1 minute OFF 30 minutes
DHW Priority Timeout OFF OFF 120 minutes
DHW Priority Enabled
DHW Call Blocking 0 minute 0 minute 30 minutes
DHW to CH Call Blocking 1 minute 0 minute 30 minutes
Antilegionella Function Disabled
HEATING SETTING FACTORY DEFAULT MINIMUM SETTING MAXIMUM SETTING
EXISTING SETTING
Heating Operation Enabled
Demand
Switch &
Outdoor Reset
Absolute Max CH Setpoint 188°F [87°C] 68°F [20°C] 188°F [87°C]
CH1 Maximum Setpoint 180°F [82°C] 68°F [20°C] 188°F [87°C]
CH1 Minimum Setpoint 120°F [49°C] 60°F [15°C] 188°F [87°C]
Reset Curve Coldest Day 0°F [-18°C] -30°F [-34°C] 50°F [10°C]
Reset Curve Warmest Day 64°F [18°C] 60°F [15°C] 78°F [25°C]
CH2 Circuit Enabled
CH2 Maximum Setpoint 140°F [60°C] 68°F [20°C] 188°F [87°C]
CH2 Minimum Setpoint 80°F [27°C] 60°F [15°C] 188°F [87°C]
Warm Weather Shutdown OFF OFF 78°F [25°C]
Pump Constant Circulation Disabled
CH Post Pump Time 1 minute OFF 20 minute
Freeze Protection Enabled
Frost Protection Setpoint -22°F [-30°C] -22°F [-30°C] 50°F [10°C]
Parallel Shift Value 0°F [0°C] 0°F [0°C] 144°F [80°C]
CH Call Blocking 1 minute 0 minute 30 minutes
System Pump CH1/CH2
CASCADE SETTING FACTORY DEFAULT MINIMUM SETTING MAXIMUM SETTING
EXISTING SETTING
Stage Delay 60 seconds 0 second 255 seconds
Minimum Firing Rate 30% 0% 100%
Maximum Firing Rate 398 MBH [117kW] 0 MBH [0kW] 869 MBH [255kW]
CH / DHW Boilers 0 0 6
Automatic Rotation
Enabled
CH Proportional Gain 7 1 255
CH Integral Gain 245 1 255
DHW Proportional Gain 7 1 255
DHW Integral Gain 245 1 255
BOILER SETTING FACTORY DEFAULT MINIMUM SETTING MAXIMUM SETTING
EXISTING SETTING
Prestige Model Solo
Lockout Temperature 210°F [99°C]
Modbus Address 0=BCST 0 247
Prestige_TriMax_Control_Display_Module_DCR639 1/14/14 9:45 AM Page 6
1.6. Default Values and Adjustments