PVC/CPVC Sidewall Vent Termination Kit Instructions

PVC/CPVC Low Profile Sidewall
Vent Termination Kit
2
Pre-Installation Guidelines
1. The vent termination location must maintain all
termination clearances stated in Section II
Direct Vent Installation of the Vent Supplement
included with the boiler.
2. Ensure vent termination location does not
exceed the maximum allowable vent length as
listed in the boiler Vent Supplement.
3. The sidewall Vent Termination is suitable for
PVC or CPVC vent systems and may be
installed in a horizontal or vertical configura-
tion as shown in Fig. 2.
When installing the vent termination in a verti-
cal configuration, ensure the vent piping is locat-
ed above the air inlet piping. This will avoid the
risk of flue gas products recirculating into the
air inlet and building.
For installations in Canada, all piping, fittings
and cement/primer material must comply with
ULC S636 certification.
Do not use cellular core piping for the venting
system.
DO NOT mix vent components from different
vent systems. Use only PVC and/or CPVC pipe
and fittings. Seal all pipe and fittings with
appropriate primer and cement. Failure to com-
ply with these requirements could cause venting
system failure resulting in leakage of flue prod-
ucts into the living space.
4. All vent piping and assembly / gluing of the
vent piping should comply with the guidelines
referenced in the boilers Vent Supplement.
5. For multiple vent termination installation, refer-
ence Figure 5 for vertical orientations and
Figure 6 for horizontal orientation.
Installation of the Vent Termination
1. Use the wall plate as a template to locate the pene-
tration holes through the outside wall. Reference
Table 1 on page 3 for the proper hole diameter.
2. Use a core drill or hole saw to cut the penetra-
tion holes through the outside wall.
When locating the penetration of the vent and air
pipes ensure the termination is properly oriented
as shown in Fig. 2. For multiple vent terminations
ensure the vent and air penetration are at the
same height. failure to do so can result in severe
personal injury or substantial property damage.
NOTICE
NOTICE
WARNING
WARNING
WARNING
Fig. 2: Installation Orientation of the Vent
Terminations