Instructions

BOILER COMMISSIONING KIT
Maintain the design specification and
energy efficiency
Restore energy efficiency
Inhibit the formation of scale and sludge
Minimize corrosion of system metals
Good practice dictates that hydronic central heating systems should be thoroughly cleaned and flushed
before installing a new boiler, after which a chemical inhibitor should be added to ensure the system
is protected from corrosion, scale and sludge build-up. These procedures should also be employed when major
work is carried out on a system. A clean, protected system helps ensure that the heat generated by the boiler is
transmitted efficiently into the house over the long term
Test Procedure
1. Prior to cleaning and flushing, use the enclosed pH test strips and color coded chart to measure the
initial pH of the system water as a reference guide.
2. Check boiler manufacturer’s instructions regarding system cleaning prior to commencing work.
3. Best practice is to clean and flush the heating system with the old boiler still installed prior to installation
of a new boiler.
4. Drain the system water.
5. Fill the system with fresh water.
6. Add Fernox Cleaner F3 into the system.
7. Run up to temperature for a minimum of one hour. Ensure that all the system is fully open to allow
complete cleaning. Check that all zones including all radiators (if present), are heating up and there are
no cold spots.
8. Drain and flush the system thoroughly in both directions to remove the cleaning agent and any debris
until the water runs clean. Use of a powerflusher is preferred.
9. Fill the system with fresh water.
10. Add Fernox Protector F1 to provide long term protection against corrosion and limescale, and maintain
efficiency. Circulate around the system for equal distribution.

Summary of content (2 pages)