Prestige TriMax Control Supplement
/A1/23'3BB7<5A
37
- To reach the setpoint faster, increase the DHW Proportional
Gain value by 2. Perform Cascade Autodetection and initiate a
domestic hot water call. Observe the cascade response and
make further adjustments if necessary.
J 31@3/A3+%@=>=@B7=</:/7<
- The Cascade System will take longer to reach the setpoint, but
setpoint overshooting is minimized.
- If the setpoint is reached too quickly, decrease the DHW
Proportional Gain value by 2. Perform Cascade Autodetection
and initiate a domestic hot water call. Observe the cascade
response and make further adjustments if necessary.
$<:G;/93/28CAB;3<BAB=B67AA3BB7<5/4B3@1=<AC:B7<5(@7/<5:3(C03
(316<71/: 'C>>=@B ;>@=>3@ /28CAB;3<B =4 + %@=>=@B7=</:
/7< 1=C:2 :3/2 B= B3;>3@/BC@3 4:C1BC/B7=<A /<2 3@@/B71 1/A1/23
=>3@/B7=<
+<B35@/:/7< 34/C:B
DHW Integral Gain allows the cascade response to be adjusted for a
domestic hot water call. DHW Integral Gain has the greatest influence
when the system temperature is close to the setpoint. Press the !( or
&( buttons to adjust the DHW Integral Gain then press the $ but-
ton to store the setting.
J <1@3/A3+<B35@/:/7<
- The Cascade System will take longer to reach the setpoint, but
setpoint overshooting is minimized.
- If the setpoint is reached too quickly, increase the DHW Integral
Gain value by 2. Perform Cascade Autodetection and initiate a
domestic hot water call. Observe the cascade response and
make further adjustments if necessary.
J 31@3/A3+<B35@/:/7<
- The Cascade System will reach setpoint faster, but overshooting
the setpoint may occur.
- To reach the setpoint faster, decrease the DHW Integral Gain
value by 2. Perform Cascade Autodetection and initiate a
domestic hot water call. Observe the cascade response and
make further adjustments if necessary.
NOTICE
1
255
245
DHW Integral Gain