Prestige TriMax Control Supplement
/A1/23'3BB7<5A
35
0
6
0
CH or DHW Boilers
=@+=7:3@A 34/C:B
The CH or DHW Boilers setting specifies how many boilers in a Split
Cascade System will respond to a domestic hot water call. The CH or
DHW Boilers always include the Master boiler. The remaining boilers
will only respond to central heating calls. This allows the Cascade
System to satisfy both central heating and domestic hot water calls at the
same time. At the completion of a domestic hot water call, the CH or
DHW Boilers will again be available to respond to central heating calls.
Press the !( or &( buttons to adjust the CH or DHW Boilers
setting then press the $ button to store the setting.
'>:7BB7<5B63/A1/23'GAB3;7<B==<:G/<2=@+0=7:3@A
@3?C7@3AB630=7:3@AB=03>7>32/AA6=E<7<75C@3>/53(63
=@ + 0=7:3@A ;CAB 03 >7>32 B= 0=B6 /<2 + :=/2A
27@31B:G4=@>@=>3@=>3@/B7=<
+ %@7=@7BG ;CAB 03 A3B B= </0:32 7< + '3BB7<5A =4 B63
/A1/23"/AB3@4=@>@=>3@=>3@/B7=<
::=@+=7:3@AE7::@3A>=<2B=/2=;3AB716=BE/B3@1/::B
7A7;>=@B/<BB6/BB632=;3AB71:=/27A1/>/0:3=4B@/<A43@@7<5/::=4
B6363/B53<3@/B32B=>@3D3<B3F13AA7D30=7:3@1G1:7<5
%@=>=@B7=</:/7< 34/C:B
CH Proportional Gain allows the cascade response to be adjusted for a
central heating call. CH Proportional Gain has the greatest influence
when the system temperature is far away from the setpoint. Press the
!( or &( buttons to adjust the CH Proportional Gain then press
the $ button to store the setting.
J <1@3/A3%@=>=@B7=</:/7<
- The Cascade System will reach setpoint faster, but overshooting
the setpoint may occur.
- To reach the setpoint faster, increase the CH Proportional Gain
value by 2. Perform Cascade Autodetection and initiate a cen-
tral heating call. Observe the cascade response and make fur-
ther adjustments if necessary.
J 31@3/A3%@=>=@B7=</:/7<
- The Cascade System will take longer to reach the setpoint, but
setpoint overshooting is minimized.
- If the setpoint is reached too quickly, decrease the CH
Proportional Gain value by 2. Perform Cascade Autodetection
and initiate a central heating call. Observe the cascade response
and make further adjustments if necessary.
NOTICE
NOTICE
NOTICE
1
255
10
CH Proportional Gain