Install Instructions

IdWH SEnSoR PaRaMETER
1. Once the access code number has been stored and
accepted in the control module, change the display
readout to “Parameter” mode by pressing MODE
WARNING
Parameter 46 has several other possible settings
available. The factory setting of the IdWH is aquas-
until the display shows
PARA
.
tat control or
_13
.
The required revised setting of
2. Press STEP to enter the first parameter setting.
Continue pressing STEP until the display shows
P_46
.
NOTICE
By pressing STEP you will sequence through the
the IdWH nTc control or
_12
. any other setting of
parameter 6 could result in erratic or unreliable
operation of the Prestige resulting in severe person-
al injury, death or substantial property damage.
parameter settings as follows:
1140
,
2_01
,
3_01
,
4186
,
P_10
,
P_11
,
P_012
.....
P_46
. The dis-
play readout will continue showing “
P
” followed by
a 2 digit number that increases after each press of
the STEP button after the fourth parameter setting.
NOTICE
The parameter setting will continue for 46 different
parameter setting. By continuing to press the STEP
button, the display readout will rollover to the first
parameter setting.
WARNING
do not attempt to revise any other control parameter
setting except those listed in this supplement.
Perform only those parameter revisions described in
this supplement. failure to comply could result in
erratic or unreliable operation of the Prestige result-
ing in severe personal injury, death or substantial
property damage.
6. To exit the Code mode, press the RESET button
once. The unit will go into a self-check mode upon
acceptance of the reset.
dHW SToRaGE TEMPERaTuRE SETTInG
The parameter setting for the domestic storage temper-
ature set point is Parameter 1 and is accessible without
having to enter the access code.
To revise the parameter setting within the Prestige
Control Module for the set point of the Domestic Storage
temperature, the installer can access the parameter set-
ting by entering the Parameter Mode
PARA
during nor-
mal operation, the access code is not required.
3. When the display readout shows
P_46
, stop press-
1. Press MODE once until the display shows
PARA
.
ing the STEP button. Wait a second and the display
will flip over to the current setting of parameter 46 in
the right two digits of the display.
4. Press the + or - button to revise the setting until the
display shows
_12
.
5. Press the STORE button to save the change. The
display will flash once to indicate the control module
accepts the change.
15
2. Press STEP until the display shows
1140
or 1XXX
(where XXX is a setting other than the factory setting).
3. Press the + or - button until the desired DHW stor-
age temperature setting is achieved. Press STORE
to save the setting. The display will flash when the
revised setting is accepted.