Install Instructions

Wire of nTc Sensor to Prestige
1. Disconnect the Snap-set connector located on the
thermostat cover plate of the SMART. One portion
of the Snap-set connector will remain mounted on
the cover plate. On the Snap-set plug portion not
mounted, use a Phillips-head screwdriver and
remove the plug cover mounting screws.
2. With the Snap-set plug cover removed, connect 18
gauge wire or thermostat type wire to the end termi-
nals C and 1 of the plug. The wire ends should be
stripped and attached securely to the terminals. See
Figure 3.
3. Replace the plug cover, ensuring the mounting
Low Voltage
Terminal Block
Terminal Block
Tool
screws are secure in place.
Fig. 4: Prestige Low Voltage Terminal
7. Once the wiring is attached to the terminal block,
reconnect the terminal block to the terminal strip.
Ensure the connection is complete and secure.
8. Replace the Prestige front jacket panel and secure
with the thumb screw.
9. Restore power to the Prestige boiler.
Fig. 3:
Smart Snap Set Connector Wiring
4. Remove the front jacket panel of the Prestige by
removing the thumb screw along the upper edge.
Once the thumb screw is removed, pull the panel
slightly forward and lift up.
5. Route the wiring from the snap-set plug to the
Prestige.
Once at the Prestige, route the wiring
through the Prestige wire access openings and
along the wire ways inside the Prestige.
6. Disconnect the bottom half of the Prestige’s low volt-
age terminal block. Strip the wire ends and attached
to the terminal block terminals 11 and 12 using the
terminal block tool supplied with the Prestige. See
Figure 4
3