Install Instructions

TRouBlESHooTInG
Error codes
If Parameter 46 setting is 12 (IDWH Sensor) the follow-
ing “soft” lockouts could occur:
b_38
alternating with a status code of 9
The IDWH Sensor is not properly connected to
the Prestige low voltage terminal strip. Check
for proper connections and terminations.
b_33
alternating with a status code of 9
The IDWH Sensor is short-circuited. Check if
the DHW is being used and is properly con-
nected to the Prestige low voltage terminals.
Ensure Parameter 35 is correctly set for 12 and
is stored properly.
Once the condition is corrected the errors will automati-
cally reset and the Prestige will return to normal operation.
19