Install Instructions

3. Press STEP until the display shows
P_43
. This
parameter setting is the “DHW Priority Timeout”
parameter. After releasing the STEP button the dis-
play will show the current setting.
4. Press the + or - button until the desired “DHW Priority
Timeout” setting is achieved. Press STORE to save
the setting. The display will flash when the revised
setting is accepted.
5. Once the desired parameter setting have been
revised and stored within the Prestige Control mod-
ule, press RESET to exit the CODE mode.
18
addITIonal dHW fEaTuRES
frost Protection
With the addition of the IDWH sensor, the Prestige Control
module will now provide a Frost Protection feature to the
SMART tank. This feature becomes active when
Parameter 46 is set to 12 and cannot be overridden.
The Frost Protection feature is designed to protect the
SMART IDWH from a potential freeze up. The protec-
tion is activated once the IDWH sensor records a
domestic temperature of 37ºF. At that time the Prestige
boiler will begin the burner function at low input and the
DHW circulator will begin circulating. The burner will
continue operating at minimum input with the DHW cir-
culator energized until the sensor senses a domestic
water temperature of 50ºF. At that point the boiler will
shut down the burner function and the DHW circulator.
This feature is always active even if the DHW operation
is in the OFF mode.
Misc. functions
There are several other Parameter settings available for
DHW applications, i.e. post pump features, blocking time
for burner operation. These features are explained more
in detail in the Prestige Control Supplement.