Product Overview
Condensate Neutralizer Kit
Kit Parts Number: PSNEU01
Parts List:
1. (1) Condensate Neutralizer
2. (1) Hose Clamp (not shown)
3. (2) Mounting Strap (not shown)
4. (2) Mounting Screw (not shown)
Condensate produced by the Prestige Boiler
typically has a pH value between 3 and 4.
The condensate neutralizer kit will treat the
condensate to a safe pH value above 6.5. In
those areas where local codes may prohibit
the discharge of untreated condensate into
the public sewage system, the installer
should check compliance when using the
condensate neutralizer kit.
NOTICE
1
Instructions:
1. Attach the boiler condensate drain hose to
the 3/4” barbed fitting on the condensate
neutralizer. Secure using the hose clamp
provided.
2. Mount the condensate neutralizer horizon-
tally near the unit, and higher than the con-
densate pump or drain. Secure using the
mounting straps and screws provided.
3. Attach 1/2” ID vinyl tubing (supplied by
others) to the 1/2” barbed fitting on the con-
densate neutralizer. Secure using a hose
clamp or wire tie. (supplied by others)
4. Run the 1/2” vinyl tubing to the condensate
pump or drain.
If the condensate drain outlet of the Prestige
Boiler is lower than the drain, the installer must
provide a condensate pump.
The depletion of the neutralization media
depends upon the operation of the Prestige
Boiler. To determine the necessary refill inter-
val, check media level several times during the
first year of operation. As a minimum the media
should be replaced annually to maintain a pH
value above 6.5 using Triangle Tube Refill Kit
Part Number PSNEU02.
NOTICE
NOTICE
2006-35 Condensate Neutralizer Kit11/2/06
1/2” Hose Bard
14 1/4”
2 1/2” O.D
3/4” Hose Bard