User Guide
Table Of Contents
- Table of Contents
- Product & Safety Information
- Homeowner
- Technician
- Service and Maintenance
- PRESTIGE Operation
- Boiler & System Water
- Section I - Combustion Air - Prevention of Contamination
- 1.1 Potential Contaminating Products
- Section II - Maintenance Schedule
- 2.1 Service Technician
- 2.1.1 General
- 2.1.2 Poor Performance or Combustion
- 2.2 Owner Maintenance
- 2.2.1 Periodic
- 2.2.2 Monthly
- 2.2.3 Every 6 Months
- Section III - Maintenance Procedures
- 3.1 Daily Maintenance
- 3.1.1 Check the Surrounding Area
- 3.1.2 Check Combustion Air Inlets
- 3.1.3 Check Temperature Display and Pressure Gauge
- 3.2 Monthly Maintenance
- 3.2.1 Check Vent Piping
- 3.2.2 Check Combustion Air Inlet Piping
- 3.2.3 Check Pressure Relief Valve
- 3.2.4 Check Condensate Drain System
- 3.2.5 Check Automatic Air Vents (If Used)
- 3.3 6-Month Maintenance
- 3.3.1 Check Water and Gas Piping
- 3.3.2 Operate Pressure Relief Valve
- Section IV - O
- Section V - ACVMax Operation
- 5.1 ACVMax Navigation
- 5.2 ACVMax Menu Structure
- 5.3 Home Screen
- 5.4 Status Line Messages
- 5.4 Main Menu
- 5.5 CH/DHW OperationāMenu
- 5.6 Boiler Information
- 5.7 Information Items
- 5.8 Lockout History
- 5.9 Lockout Screen
- 5.10 Manual Reset Hard Lockouts
- 5.11 Automatic Reset Soft Lockouts
- Section VI - Replacement Parts
- Parts
- Solo 80/110 Jacket Components
- Solo 155/175/250 Jacket Components
- Solo 299/399 Jacket Components
- Solo 80/110 Internal Components
- Solo 155/175/250 Internal Components
- Solo 299/399 Internal Components
- olo 80/110 & Excellence Burner Components
- Solo 155/175/250 Burner Components
- Solo 299/399 Burner Components
- Control Module Enclosure
- Display Module Enclosure
- Table of Contents
5
2.0 Maintenance Schedule
SECTION II - MAINTENANCE
SCHEDULE
2.1 Service Technician
At least on an annual basis the following maintenance
should be performed by a qualified service technician:
2.1.1 General
- Attend to any reported problems.
- Inspect the interior of the boiler jacket area; clean
and vacuum if necessary.
- Clean the condensate trap and fill with fresh water.
- Check boiler fluid pH on systems.
- Check for leaks: water, gas, flue and condensate;
check connections and piping inside and outside of
the casing.
- Verify flue vent piping/gaskets and air inlet piping are
in good condition, sealed tight and properly supported.
- Check internal flue pathways for condition and proper
sealing: condensate pan, vent pipe, and vent adapter.
- Check boiler water pressure, piping and expansion
tank.
- Check control settings.
- Check ignition electrode (sand off any white oxide;
clean and reposition).
- Check ignition wiring and ground wiring.
- Check all control wiring and connections.
- Check burner flame pattern (stable and uniform).
2.1.2 Poor Performance or Combustion
- Clean heat exchanger and flue ways.
- Remove burner assembly and clean burner head
using compressed air only.
Once the maintenance items are completed, review the
service with the owner.
2.2 Owner Maintenance
2.2.1 Periodic
- Check the area around the unit.
- Check and remove any blockage from the combus-
tion air inlet and ventilation openings.
- Check the temperature/pressure gauge.
2.2.2 Monthly
- Check vent piping.
- Check combustion air inlet piping.
- Check the pressure relief valve.
- Check the condensate drain system.
2.2.3 Every 6 Months
- Check boiler piping and gas supply piping for corro-
sion or potential signs of leakage.
- Operate the pressure relief valve.
Follow the maintenance procedures given
throughout this manual. Failure to perform the
service and maintenance or follow the directions
in this manual could result in damage to the
PRESTIGE or in system components, resulting
in severe personal injury, death or substantial
property damage.
WARNING