Prestige Venting Supplement
16
CHAPTER 2
CHAPTER 2 - DIRECT VENT INSTALLATION OF VENT/AIR PIPING
Vent Termination
Bird Screen
The installer must install the factory supplied “bird
screens” on the vent and combustion air terminations.
NOTICE
Combustion
Air
Termination
Bird Screen
Vent Termination Typ.
Combustion Air Termination Typ.
12" [30.5 cm] (18” [45.7 cm] Canada)
Above the Highest
Anticipated Snow Level
12" Min. [30.5 cm]
Typ.
12" Min. [30.5 cm]
Radial Distance
12" Min. - 24” Max.
[30.5 cm - 61 cm]
Above Combustion
Air Inlet Typ.
Fig. 3 - Vertical Vent Bird Screen Installation Fig. 4 - Vertical Combustion Air Bird Screen Installation
Fig. 5 - Direct Vent - Vertical Termination of Multiple Prestige Boilers