Prestige Excellence Series Installation Manual
80
Product Specifications
DOE
Fuel
D
OE
H
eating Capacity
Note 1 & 4
Input
Note 4
DOE Seasonal
Efficiency AFUE
Note 3
Net AHRI
Rating
Note 2
99,000
110,000
95%
Shipping
Weight
Lbs/Kg
190/86
Natural
B
oiler
Model
Excellence
86,000
87,000
97,000
95%
190/86
Propane Excellence
76,000
Note 1: The heating capacity of the PRESTIGE
Excellence is based on the test requirements
of the U.S. Department of Energy.
Note 2: The AHRI rating is based on a piping and
pick up allowance of 1.15. This allowance
should be sufficient for the standard radiation
requirements for a building load.
Note 3: Based on the given AFUE the PRESTIGE
Excellence meets the energy efficiency
guidelines established by Energy Star.
Note 4: Input and output ratings are shown for sea
level applications. The PRESTIGE
Excellence automatically derates the input at
approximately 2% for every 1,000 Ft. of alti-
tude. No alterations to the boiler or burner
system is required.