Prestige Excellence Series Installation Manual
44
Trimax Operation
Select CH1 Reset Curve Default: Finned Tube Baseboard
Select CH1 Reset Curve prompts the installer to select an outdoor reset curve
for a CH1 heating call when an Outdoor Reset option is chosen in Select CH
Demand. Outdoor reset curve presets are available to cover most applica-
tions. The outdoor reset curve can also be adjusted to any desired settings in
the Installer Menu. Press the UP or DOWN buttons to select the outdoor
reset curve appropriate for the type of heating system then press the OK but-
ton to store the setting.
Select CH2 Reset Curve Default: Low Mass Radiant
Select CH2 Reset Curve prompts the installer to select an outdoor reset curve
for a CH2 heating call when an Outdoor Reset option is chosen in Select CH
Demand. Outdoor reset curve presets are available to cover most applica-
tions. The outdoor reset curve can also be adjusted to any desired settings in
the Installer Menu. Press the UP or DOWN buttons to select the outdoor
reset curve appropriate for the type of heating system then press the OK but-
ton to store the setting.
Set Warm Weather Shutdown Temperature Default: OFF
Warm Weather Shutdown prompts the installer to enter an optional outdoor
temperature at which to disable the central heating function and any circu-
lators placed into constant circulation with the pump constant circulation
setting. The Prestige will continue to respond to a domestic hot water call
or a 0-10V Modulation Signal when the outdoor temperature exceeds the
Warm Weather Shutdown Temperature setting. Press the LEFT or
RIGHT buttons to adjust the Warm Weather Shutdown Temperature then
press the OK button to store the setting. The Warm Weather Shutdown
icon is displayed on the home screen when the outdoor temperature
reaches the Warm Weather Shutdown Temperature.
180ºF
120ºF
64ºF
0ºF
Current Settings
Table 3: Outdoor Reset Preset Selections
Preset Minimum Setpoint Maximum Setpoint
Low Mass Radiant 80ºF [27ºC] 140ºF [60ºC]
High Mass Radiant 80ºF [27ºC] 120ºF [49ºC]
Cast Iron Baseboard 100ºF [38ºC] 170ºF [77ºC]
Finned Tube Baseboard 120ºF [49ºC] 180ºF [82ºC]
Radiators 120ºF [49ºC] 170ºF [77ºC]
Fan Coil 140ºF [60ºC] 180ºF [82ºC]
Off 78ºF
Off
Warm Weather Shutdown