Prestige ACVMax Control Supplement
6.0 Factory ACVMax Settings
37
6.0 FACTORY ACVMAX SETTINGS
Section Setting Factory Default
Minimum
S
etting
Maximum
S
etting
EZ Setup
R
eset
Installer
R
eset
2
.2 Heating Operation Enabled
3
2.3 Demand Type Thermostat & Outd. Curve
33
2.4 Absolute Max CH Setpoint 188°F [87°C] 68°F [20°C] 188°F [87°C]
2.5 CH1 Maximum Setpoint 180°F [82°C] 68°F [20°C] 188°F [87°C]
33
2.6 CH1 Minimum Setpoint 80°F {27°C] 60°F [15°C] 188°F [87°C]
33
2.7 Outdoor Curve Coldest Day 10°F [-12°C] -30°F [-34°C] 50°F [10°C]
3
2.8 Outdoor Curve Warmest Day 64°F [18°C] 60°F [15°C] 78°F [25°C]
3
2.9 CH2 Circuit Enabled
3
2.10 CH2 Maximum Setpoint 140°F [60°C] 68°F [20°C] 194°F [90°C]
33
2.11 CH2 Minimum Setpoint 80°F [27°C] 60°F [15°C] 190°F [88°C]
33
2.12 Warm Weather Shutdown OFF OFF 78°F [25°C]
33
2.13 Circulation Pump Permanent Disabled
3
2.14 CH Post Pump Time 5 Minute OFF 20 minutes
3
2.15 Freeze Protection Enabled
3
2.16 Frost Protection Setpoint -22°F [-30°C] -22°F [-30°C] 50°F [10°C]
3
2.17 Parallel Shift Value 0°F [0°C] 0°F [0°C] 144°F [80°C]
3
2.18 CH Call Blocking 2 Minute 0 minute 30 minutes
3
3.2 DHW Operation Enabled
3
3.3 Demand Type
Thermostat (Solo)
Sensor (Excellence)
3.4 Boiler DHW Setpoint 168°F [76°C] 96°F [35°C] 188°F [87°C]
33
3.5 DHW Setpoint 140°F [60°C] 68°F [20°C] 176°F [80°C]
33
3.6 DHW On Differential 6°F [3°C] 4°F [-15°C] 18°F [-8°C]
3
3.7 DHW Storage Adder 28°F [15°C] 10°F [0°C] 54°F [30°C]
3
3.8 DHW Post Pump Time 2 Minute OFF 120 minutes
3
3.9 DHW Priority Timeout Off OFF 120 minutes
33
3.10 DHW Priority Enabled
3
3.11 DHW Call Blocking 0 Minute 0 minute 30 minutes
3
3.12 DHW to CH Call Blocking 1 Minute 0 minute 30 minutes
3
3.13 Antilegionella Function Disabled
3*
7.5.2 Stage Delay 60 Seconds 0 second 255 seconds
3
7.5.3 Minimum Firing Rate 25% 0% 100%
3
7.5.6 Maximum Firing Rate 852 MBH [250kW] 0 MBH [0kW]
869 MBH
[255kW]
3
7.5.7 CH/DHW Boilers 006
3
7.5.8 Automatic Rotation Enabled
3
7.5.9 CH Proportional Gain 70255
3
7.5.10 CH Integral Gain 245 0 255
3
7.5.11 DHW Proportional Gain 70255
3
7.5.12 DHW Integral Gain 245 0 255
3
4.2 Prestige Model
Solo (2 pumps)
3**
Solo/Excel. (3 way valve)
4.3 Lockout Temp. 210°F [99°C]
3
4.4 Modbus Address 0=BCST 0 247
3
4.5 Pump Settings Solo/Excellence 2
3
4.6 Ignition Level NAT
* Installer Reset will reset value to Enabled.
** Installer Reset will reset value to Solo (2 pumps).