13.0 External Modulating Control
664A0100 - Rev. A
Factory ACVMax Setting
HEATING SETTING FACTORY DEFAULT EZ SETUP RESET INSTALLER RESET
Heating Operation
Enabled
3
Demand Type
Thermostat &
Outd. Curve
3 3
Absolute Max CH Setpoint
188°F [87°C]
CH1 Maximum Setpoint
180°F [82°C]
3 3
CH1 Minimum Setpoint
120°F [49°C]
3 3
Outdoor Curve Coldest Day
0°F [-18°C]
3
Outdoor Curve Warmest Day
64°F [18°C]
3
CH2 Circuit
Enabled
3
CH2 Maximum Setpoint
140°F [60°C]
3 3
CH2 Minimum Setpoint
80°F [27°C]
3 3
Warm Weather Shutdown
OFF
3 3
Circulation Pump Permanent
Disabled
3
CH Post Pump Time
5 Minute
3
Freeze Protection
Enabled
3
Frost Protection Setpoint
-22°F [-30°C]
3
Parallel Shift Value
0°F [0°C]
3
CH Call Blocking
1 Minute
3
DOMESTIC SETTING FACTORY DEFAULT EZ SETUP RESET INSTALLER RESET
DHW Operation
Enabled
3
Demand Type
Thermostat (Solo)
Sensor (Excellence)
Boiler DHW Setpoint
167°F [75°C]
3 3
DHW Setpoint
140°F [60°C]
3 3
DHW On Differential
6°F [3°C]
3
DHW Storage Adder
28°F [15°C]
3
DHW Post Pump Time
1 Minute
3
DHW Priority Timeout
Off
3 3
DHW Priority
Enabled
3
DHW Call Blocking
0 Minute
3
DHW to CH Call Blocking
1 Minute
3
Antilegionella Function
Disabled
3
BOILER SETTING FACTORY DEFAULT EZ SETUP RESET INSTALLER RESET
Prestige Model
Solo (2 pumps)
Solo/Excel. (3 way valve)
3
Lockout Temp.
210°F [99°C]
3
Modbus Address 0=BCST
3
Pump Settings Solo/Excellence 2
3
Ignition Level NAT