Full Product Manual
56
10.0 Start-Up Preparation
664A0100 - Rev. A
10.3 Check Low Water Cut-Off Device
- The PRESTIGE Excellence is provided
with a factory installed LWCO device that
monitors system pressure.
- Access the Boiler Information Menu by fol-
lowing instructions in Section 9.12 on page
48. Scroll down to see the current system
pressure displayed and verify it is within the
recommended numbers given in Section 10.2
on page 53.
10.4 Check For Gas Leaks
Prior to start-up and during initial opera-
tion, smell near the floor and around the
unit for gas odorant or any unusual odor.
Do not proceed with the start-up if there
is any indication of a gas leak. Any leaks
found must be repaired immediately.
Propane installations only - The propane
supplier mixes an odorant with the
propane to make its presence detectable.
In some cases the odorant can fade and
the gas may no longer have an odor.
Prior to start-up of the unit and periodi-
cally after start-up have the propane sup-
plier check and verify the odorant level.
10.5 Check Thermostat Circuit
- Disconnect the external thermostat wires
from the low voltage terminal strip.
- Connect a voltmeter across the wire ends of
the external thermostat wiring.
- Close each thermostat, zone valve and
relay in the external circuit one zone at a
time and check the voltage reading across
the wire ends.
- There should NEVER be voltage measured
at the wire ends.
- If voltage is measured at the panel under any
condition, check and correct the external wiring.
In systems using 3-wire zone valves, back-
feed of voltage to the unit is a common
problem. Use an isolation relay to prevent
voltage from the external circuit entering
the PRESTIGE Excellence control panel.
- Reconnect the external thermostat wires to
the low voltage terminal strip.
10.6 Inspection of Condensate Drain
Assembly
1. Inspect and ensure the Condensate Drain
Assembly is properly installed as described
on page 22 and shown in Fig. 11 on page 23.
2. Remove the plug from the Condensate
Drain Assembly and fill with fresh water.
The condensate drain assembly must be
filled with water when the PRESTIGE
Excellence is in operation. The conden-
sate drain assembly prevents flue gas
emissions from entering the condensate
line. Failure to ensure trap is filled with
water could result in severe personal
injury or death.
3. Re-Install plug in condensate drain assem-
bly.
NOTICE
WARNING
WARNING
NOTICE