Full Product Manual
664A0300 - Rev. B
Additional DHW Feature
15
Factory ACVMax Setting
DOMESTIC SETTING FACTORY DEFAULT EZ SETUP RESET INSTALLER RESET
DHW Operation Enabled
Demand Type
Thermostat (Solo)
Sensor (Excellence)
Boiler DHW Setpoint 167°F [75°C]
DHW Setpoint 140°F [60°C]
DHW On Differential 6°F [3°C]
DHW Storage Adder 28°F [15°C]
DHW Post Pump Time 1 minute
DHW Priority Timeout OFF
DHW Priority Enabled
DHW Call Blocking 0 minute
DHW to CH Call Blocking 1 minute
Antilegionella Function Disabled
BOILER SETTING FACTORY DEFAULT EZ SETUP RESET INSTALLER RESET
Prestige Model
Solo (2 pumps)
Solo/Excel. (3-way valve
Lockout Temperature 210°F [99°C]
Modbus Address 0=BCST
Pump Settings Solo/Excellence 2
Ignition Level NAT
HEATING SETTING FACTORY DEFAULT EZ SETUP RESET INSTALLER RESET
H
eating Operation
E
nabled
Demand Type
T
hermostat & Outdoor
Reset
Absolute Max CH Setpoint 188°F [87°C]
CH1 Maximum Setpoint 180°F [82°C]
CH1 Minimum Setpoint 120°F [49°C]
Outdoor Curve Coldest Day 0°F [-18°C]
Outdoor Curve Warmest Day 64°F [18°C]
CH2 Circuit Enabled
CH2 Maximum Setpoint 140°F 60°C]
CH2 Minimum Setpoint 80°F [27°C]
Warm Weather Shutdown OFF
Circulation Pump Permanent Disabled
CH Post Pump Time 5 Minutes
Freeze Protection Enabled
Frost Protection Setpoint -22°F [-30°C]
Parallel Shift Value 0°F [0°C]
CH Call Blocking 1 Minute