Prestige Solo 110 Condensing Gas Boiler 89

C
B
A
D
E
F
G
H
J
I
M
K
L
2
Boiler Specifications
Side ViewFront View
2
4
6
8
10
12
14
16
P
ressure Drop (Ft. W.C.)
Solo 110
G
0
2
45678910 11 12
P
Flow Rate (GPM)
Pressure Drop Curve vs Grundfos UPS 15-58-FC
Boiler Dimensions
Letter Connection
Dimension
in [mm]
A
3/4" NPSC
Pressure Relief
Valve
16-5/8"
[
423]
B
3" Combustion
Air Inlet
15-13/16"
[402]
C
3" Vent Outlet
8-13/16"
[224]
D
1" NPT Boiler
Return
2-7/8"
[73]
E
1/2" NPT Gas
Connection
5-7/8"
[150]
F
1" NPT Boiler
Supply
16-7/16"
[418]
G
Boiler Width
19-3/4"
[502]
H
Boiler Height
36-9/16"
[928]
I
3/4" NPSC
Pressure Relief
Valve
11-1/4"
[286]
J
3" Combustion
Air Inlet &
3" Vent Outlet
5-9/16"
[141]
K
1/2" NPT Gas
Connection
4"
[102]
L
1" NPT Boiler
Return & Supply
13-7/16"
[341]
M
Boiler Depth
17-5/16"
[440]
Solo (('
Grundfos UPS15-58F/FC - Spd 1
Grundfos UPS15-58F/FC - Spd 2
Grundfos UPS15-58F/FC - Spd 3
Model Fuel
Input
Modulation
(MBH)
AFUE
DOE Heating
Capacity (MBH)
Net
AHRI
(MBH)
Boiler Water
Volume (gal)
Power
Shipping Weight
Lbs
Solo 110
Natural
Propane
20 - 110 95% 102 89 2.1
120/1/60
FLA: 10A
103