Install Instructions (Venting)
34
5.0 Manifold Combustion Air
5.3 Horizontal Air Termination
-
The common combustion air manifold must termi-
nate on a horizontal/side wall using a 90 degree
elbow pointed downward.
- The inlet of the common combustion air termination
e
lbow must include a corrosion resistant field sup-
plied bird screen.
- The edge of the combustion air termination cou-
pling must extend 1” (2.5 cm) beyond the finished
exterior wall as shown in Fig. 6 on page 19.
- The bottom of the common combustion air termi-
nation (inlet) must be located 12” (30.5 cm) mini-
mum above grade/highest anticipated snow level.
- The common combustion air termination must be a
minimum of 3 feet (0.9 m) below (vertically) any
appliance vent termination within 10 feet (3 m) hor-
izontally.
- The common combustion air termination must be a
minimum of 3 feet (0.9 m) horizontally from any
appliance vent termination.
- Avoid locating the common combustion air termi-
nation in a location where prevailing winds could
affect the performance of the boilers or cause recir-
culation of flue gases, such as inside corners of
buildings, near adjacent buildings, vertical surfaces,
window wells, stairwells, alcoves, courtyards, or
other recessed areas. The common air termination
must be installed a minimum of 6 feet horizontally
from any such locations.
- Locate the combustion air termination in a manner
so as to protect from damage from foreign objects,
such as stones, balls, buildup of leaves or sedi-
ment.
5.4 Installation Guidelines
- Use perforated metal strap hangers or equivalent
p
ipe hangers suitable for plastic pipe to support the
common air manifold. Hangers must be placed at a
m
aximum of every 5 ft [1.5 m] of horizontal and ver-
tical run of piping. A support must be placed at every
boiler and at every change in direction vertically or
horizontally.