Install Instructions

Table Of Contents
87
19.0 Product Specifications
Boiler
Model
F
uel
I
nput
DOE
Heating Capacity
Net AHRI
Rating
DOE Seasonal
Efficiency AFUE
Shipping
W
eight
Lbs / Kg
Solo 80
Natural
Propane
80,000 72,000 63,000 95% 103 / 47
Solo 110
Natural
Propane
110,000 99,000 86,000 95% 103 / 47
Solo 155
Natural
Propane
153,000 138,000 120,000 95% 118 / 53.5
Solo 175
Natural
Propane
170,000 154,000 134,000 95% 128 / 58
Solo 250
Natural
Propane
240,000 218,000 190,000 95% 140 / 63.5
Solo 299
Natural
Propane
299,000 272,000 237,000 95% 210 / 95
SECTION XIX PRODUCT SPECIFICATIONS
Boiler
Model
Fuel Input Output
Net AHRI
Rating
Combustion
Efficiency
Thermal
Efficiency
Shipping
Weight
Lbs / Kg
Solo 399
Natural
Propane
399,000 379,000 330,000 94.1% 95.1% 216 / 98
Note 1: The heating capacity of the PRESTIGE Solo
80/110/155/175/250 is based on the test
requirements of the U.S. Department of
Energy.
Note 2: The AHRI rating is based on a piping and
pick up allowance of 1.15. This allowance
should be sufficient for the standard radiation
requirements for a building load.
Note 3: Based on the given AFUE the PRESTIGE
Solo 80/110/155/175/250 meets the energy
efficiency guidelines established by Energy
Star.
Note 4: Input and output ratings are shown for sea
level applications. The PRESTIGE Solo
automatically derates the input at approxi-
mately 2% for every 1,000 Ft. of altitude. No
alterations to the boiler or burner system is
required.
Note 5: PRESTIGE Solo 399 output rating is based
off of the thermal efficiency.
DOE