CHAPTER 3
3.3.3 Check Condensate Drain System
1. Ensure condensate drain assembly is rmly secured
to bottom of the unit. See Fig. 1 on the right. Ensure
the Retention clip is secure. See Fig. 2 (Solo Models
only).
Do not operate the boiler without the fac-
tory-supplied condensate drain assembly
installed. Operation of the boiler without
the condensate drain assembly installed can
result in property damage, serious injury, or
death.
2. While the unit is running, check the discharge end
of the condensate drain tubing. Ensure no ue gas
is leaking from the condensate drain tubing by
holding your ngers near the opening.
3. If you notice ue gas leaking, turn o the unit and
contact a qualied service technician to inspect the
unit and condensate drain assembly.
4. Ensure the condensate drain tubing is not blocked
by pouring water through the ll plug port on the
condensate drain assembly. The water should ow
out of the end of the drain tubing. If water does
not appear at the end of the drain tubing, contact
a qualied service technician to inspect and clean
the condensate drain assembly.
5. To ll the condensate drain assembly, remove the ll
plug from the condensate assembly. Slowly pour wa-
ter into the assembly until water appears at the end
of the drain tubing. Stop lling and replace plug.
WARNING
CHAPTER 3 - MAINTENANCE PROCEDURES
FILL PLUG WITH VACCUM
BREAK PORT
SEALS
COMPRESSION NUT
WITH RUBBER SEAL
Flexible tubing
(or 3/4 PVC/
CPVC Piping to
Drain)
CONDENSATE
DRAIN ASSEMBLY
RETENTION
CLIP
FOR SOLO
MODELS ONLY
REFER TO FIG. 2
RETAINING NUT
PLASTIC BALL
NOT SHOWN
Fig. 1 - Condensate Drain Assembly
RETENTION
CLIP
FOR SOLO
MODELS ONLY
Fig. 2 - Condensate Retention Clip - (Solo Models only)
RETAINING NUT