CTRLMax Manual
26
CHAPTER 5
CHAPTER 5 - BOILER SETTINGS
Boiler Settings
Boiler Settings
Boiler Settings
Model Prstige Solo
Lockout Temp. 210°F [99°C]
Modbus Address 0=BCST
Pump settings
Ignition Level 3500rpm
Mix zone high limit 45°C
Boiler Settings
Model Prstige Solo
Lockout Temp. 210°F [99°C]
Modbus Address 0=BCST
Pump settings
Ignition Level 3500rpm
Mix zone high limit 45°C
Pump Settings
Current Pump Cong Modied
Preset Pump Cong
Flexible Pump Cong
Pump PWM minimum 40%
Pump Settings
Current Pump Cong Modied
Preset Pump Cong
Flexible Pump Cong
Pump PWM minimum 40%
Flexible Pump Cong
Flex. Relay 2 (DHW)
Flex. Relay 3 (P3)
Flex. Relay 4 (ERR)
Flex. Relay 5 (Flame)
Flex. Relay 6 (P4)
Error Relay
Error Relay
On Lockout, Blocking and Warning
On Lockout and Blocking
On Lockout
Boiler Settings
Model Prestige Solo
Lockout Temp. 210°F [99°C]
Modbus Address 1
Pump settings
Ignition Level 3500rpm
Mix zone high limit 114°F
Ignition Level
3500rpm
1500rpm 5700rpm
Pump PWM minimum
40%
1% 100%
There are three possible selections to activate the Error Re-
lay (alarm) contact:
• On Lockout, Blocking and Warning: the error relay is
activated at a non-volatile lock-out (e.g. CH Flow NTC
defect), at a blocking error (self-resetting errors) (e.g.
Gas-pressure switch not closed ), or at a warning (e.g.
low water pressure warning).
• On Lock-out and blocking: the error relay is activated
at a non-volatile lock-out or a blocking error.
• On Lockout: the error relay is activated at a non-vola-
tile lock-out only.
The selection depends on the alarm feedback requirement
from the customer.
Scroll through the settings using the UP or DOWN keys,
then validate the selection with the OK key.
The Ignition Level parameter allows to change the fan
start speed of the appliance. The default value depends on
the model and varies according to the table below.
Adjust the Ignition Level value using the LEFT or RIGHT
keys, then store the setting with the OK key.
Default: See table below for each the fan speed applicable
to each appliance/gas combination.
Although the function and the screen are dis-
played, this function is not in use. Any change
made to the value will not affect the opera-
tion of the appliance
Natural Gas Propane
Prestige Solo 80 3500 rpm 3500 rpm
Prestige Solo/Excellence 110 3500 rpm 3500 rpm
Prestige Solo 155 3800 rpm 3800 rpm
Prestige Solo 175 3800 rpm 3800 rpm
Prestige Solo 250 3800 rpm 3800 rpm
Prestige Solo 299 2500 rpm 2500 rpm
Prestige Solo 399 2650 rpm 2650 rpm
HeatMaster 240 TC 3700 rpm 3700 rpm
HeatMaster 399 TC 2000 rpm 2000 rpm
Instinct Solo 3250 rpm 3250 rpm
Instinct Combi 3250 rpm 3250 rpm