Instinct Venting Manual
4
CHAPTER 1
CHAPTER 1 - PRE-INSTALLATION REQUIREMENTS
1.4. Vent/Combustion Air Equivalent
Lengths
• For all venting applications, PVC/CPVC or AL29-
4C® Stainless Steel the length must not exceed the
lengths listed in Table 2 below.
• For PVC/CPVC or AL29-4C® vent systems, reduce
the maximum allowable length for each elbow as
follows:
• 3 feet for every 45º elbow
• 5 feet for every 90º elbow
1.5. Vent Restrictions
1.5.1 2 Inch Vent System Restrictions
• The 2 inch vent system requires a 1 inch clearance
to combustibles.
• Use long sweep elbows to limit pressure drop and
to avoid excessive vent temperatures.
• In 2 inch PVC vent applications, the rst 7 equivalent
feet of the vent system must utilize CPVC material.
To avoid vent failure, the installer must use
CPVC vent material for the first 7 equivalent
feet of a 2 inch PVC vent system. The installer
must also utilize primer and glue that is cer-
tified for both PVC/CPVC materials. Failure to
comply with this requirement can cause the
venting system to fail, resulting in substantial
property damage, serious injury, or death.
WARNING
Table 2 - Maximum Allowable Vent or Combustion Air Piping Length
INSTINCT
Model
2 Inch [60 mm] Piping
OR
3 Inch [80 mm] Piping
Feet Elbows Feet Elbows
Solo 110 33 0 100 0
Solo 155 33 0 100 0
Solo 199 N/A N/A 100 0
Combi 155 33 0 100 0
Combi 199 N/A N/A 100 0