CTRLMax Manual

65
CHAPTER 8
CHAPTER 8 - CASCADE
Cascade Settings
?
Cascade Setting
Minimum Firing Rate
10%
Max. Firing Rate 250 kW
CH / DHW Boilers 0
Auto Rotation Enabled
CH prop. Gain 7
CH Integral Gain 245
WARNING!
ONLY ADJUST THIS SETTING
WHEN INSTRUCTED TO BY
TECHNICAL SUPPORT.
P
RESS OK BUTTON TO ADJUST
SETTING, ANY OTHER BUTTON TO
KEEP CURRENT SETTINGS.
CH Integral Gain
245
1 255
CH Integral Gain allows the cascade response to be ad-
justed for a central heating call. CH Integral Gain has the
greatest inuence when the system temperature is close to
the setpoint.
Adjust the CH Integral Gain value using the LEFT or RIGHT
keys, then store the setting with the OK key.
Increase CH Integral Gain
- The Cascade System will take longer to reach the set-
point, but setpoint overshooting is minimized.
- If the setpoint is reached too quickly, increase the CH In-
tegral Gain value by 2. Perform Cascade Autodetection
and initiate a central heating call. Observe the cascade
response and make further adjustments if necessary.
Decrease CH Integral Gain
- The Cascade System will reach setpoint faster, but over-
shooting the setpoint may occur.
- To reach the setpoint faster, decrease the CH Integral
Gain value by 2. Perform Cascade Autodetection and
initiate a central heating call. Observe the cascade re-
sponse and make further adjustments if necessary
Default: 245
Please consult Triangle Tube’s technical Support
before making any adjustments. Improper adjust-
ment of CH Integral Gain could lead to temperature
fluctuations and erratic cascade operation.