CTRLMax Manual
63
CHAPTER 8
Cascade Settings
?
Cascade Setting
Stage Delay 60 sec
Minimum Firing Rate 18%
Max. Firing Rate 398 MBH
CH / DHW Boilers 0
CH Prop. Gain 7
Auto Rotation Enabled
CH / DHW Boilers
0
0 6
The CH / DHW Boilers setting species how many boilers in a
Split Cascade System will respond to a domestic hot water call.
The CH / DHW Boilers always include the Master boiler. The
remaining boilers will only respond to central heating calls. This
allows the Cascade System to satisfy both central heating and
domestic hot water calls at the same time. At the completion of
a domestic hot water call, the CH or DHW Boilers will again be
available to respond to central heating calls.
Adjust the CH/DHW Boilers number using the LEFT or RIGHT
keys, then store the setting with the OK key.
CHAPTER 8 - CASCADE
CTRLMax_w Instinct_UK version_222171_A01.indd 63 18/07/2019 18:38