CTRLMax Manual
54
CHAPTER 7
CHAPTER 7 - RESET ALL SETTINGS
DHW SETTING FACTORY DEFAULT
MINIMUM
SETTING
MAXIMUM
SETTING
EZ SETUP
RESET
INSTALLER
RESET
Prestige
Solo
Prestige
Excellence
HeatMaster
TC
Instinct
Solo
Instinct
Combi
DHW Operation Enabled
3
Demand Type Thermostat Sensor Sensor Thermostat —
DHW Boiler Setpoint 168°F [75°C] 168°F [75°C] 168°F [75°C] 168°F [75°C] — 96°F [35°C] 188°F [87°C]
3 3
DHW Setpoint 140°F [60°C] 68°F [20°C] 186°F [85°C]
3 3
DHW maximum capacity 100% 100% 100% 100% — 0% 100%
DHW On Dierential 6°F [3°C] 6°F [3°C] 6°F [3°C] 6°F [3°C] 18°F [10°C] 4°F [2°C] 18°F [10°C]
3
DHW Warmstart Setpoint — — — — 125°F [52°C] 86°F [30°C] 140°F [60°C]
DHW Warmstart Hysteresis — — — — 30°F [17K] 9K 36K
DHW Storage Adder 27°F [15°C] 27°F [15°C] 27°F [15°C] 27°F [15°C] — 10°F [5°C] 54°F [30°C]
3
DHW Post pump time 2 Minutes Off 30 Minutes
DHW Priority Timeout O Off 120 Minutes
3 3
DHW Priority Enabled
3
DHW Call Blocking 1 Minute 0 Minute 30 Minutes
3
DHW to CH Call Blocking 1 Minute 0 Minute 30 Minutes
3
Antilegionella Function Disabled Disabled Disabled Disabled — Enabled
3
DHW ramp up O O O O — Off 54°F [30°C]
BOILER SETTING FACTORY DEFAULT
MINIMUM
SETTING
MAXIMUM
SETTING
EZ SETUP
RESET
INSTALLER
RESET
Prestige
Solo
Prestige
Excellence
HeatMaster TC
Instinct
Solo
Instinct
Combi
Lockout Temp. 210°F [99°C]
3
Modbus Address 0=BCST 0=BCST 247
3
Flex. Relay 1(CH) CH1
Flex. Relay 2 (DHW) DHW
Flex. Relay 3 (P3) CH1/CH2/DHW — —
Flex. Relay 4 (ERR) ERROR — —
Flex. Relay 5 (Flame) FLAME
Flex. Relay 6 (P4) CH2 — —
Error Relay On Lockout, Blocking and Warning
Ignition Level NAT Varies by model
Mix Zone High Limit 114°F [45°C] 68°F [20°C] 176°F [80°C]
WP di trigger 0cpsi 0cpsi 290cpsi 0cpsi 0cpsi 0cpsi 725cpsi
Altitude 0ft 0ft 19680ft
CASCADE SETTING
FACTORY
DEFAULT
MINIMUM
SETTING
MAXIMUM
SETTING
EZ SETUP RESET INSTALLER RESET
Stage Delay 60 Seconds 0 Seconds 255 Seconds
3
Minimum Firing Rate 18% 0% 100%
3
Max. Firing Rate Varies by model 0 MBH [0kW] 869 MBH [255kW]
3
CH/DHW Boilers 0 0 6
3
Auto. Rotation Enabled
3
CH Prop. Gain 7 1 255
3
CH Integral Gain 245 1 255
3
DHW Prop. Gain 7 1 255
3
DHW Integral Gain 245 1 255
3
CTRLMax_w Instinct_UK version_222171_A01.indd 54 18/07/2019 18:38