CTRLMax Manual
53
CHAPTER 7
CHAPTER 7 - RESET ALL SETTINGS
Reset All Settings allows the installer to reset all CH, DHW,
and Cascade settings back to the default values (See below).
Follow the on-screen instructions to reset all settings back
to the factory default values.
Reset All Settings
Reset All Settings
Press OK to restore factory settings,
any other button to keep current
settings.
HEATING SETTING
FACTORY
DEFAULT
MINIMUM
SETTING
MAXIMUM
SETTING
EZ SETUP
RESET
INSTALLER
RESET
Prestige
Solo
Prestige
Excellence
HeatMas-
ter TC
Instinct
Solo
Instinct
Combi
Heating Operation Enabled
3
Demand Type Thermostat & Outd. Curve
3 3
CH max. capacity 100% 0% 100%
CH min capacity 0% 0% 100%
Absolute Max CH Setpoint 186°F [85°C] 68°F [20°C] 188°F [87°C] 186°F [85°C]
3
CH1 Maximum Setpoint 180°F [82°C] 68°F [20°C] 188°F [87°C] 180°F [82°C]
3
CH1 Minimum Setpoint 80°F [27°C] 60°F [15°C] 188°F [87°C]
3 3
Outdoor Curve Coldest Day 10°F [-12°C] -30°F [-34°C] 50°F [10°C]
3
Outdoor Curve Warmest Day 64°F [18°C] 60°F [15°C] 78°F [25°C]
3
CH2 Circuit Enabled
3
CH2 Maximum Setpoint 140°F [60°C] 68°F [20°C] 188°F [87°C]
3 3
CH2 Minimum Setpoint 80°F [27°C] 60°F [15°C] 186°F [88°C]
3 3
Warm Weather Shutdown O O 78°F [25°C]
3 3
Circulation Pump Permanent Disabled
3
CH Post Pump Time 5 Minutes O 20 Minutes
3
Freeze Protection Enabled
3
Frost Protection Setpoint -22°F [-30°C] -22°F [-30°C] 50°F [10°C]
3
Parallel Shift Value 0°F [0°C] 0°F [0°C] 144°F [80°C]
3
CH Call Blocking 2 Minutes 0 Minute 30 Minutes
3
Appliance min CH Setpoint 60°F 60°F 188°F
7.1. Factory CTRLMax Settings
CTRLMax_w Instinct_UK version_222171_A01.indd 53 18/07/2019 18:38