CTRLMax Manual

Dry Contact
Zone Valve
End Switches
Low Voltage Terminals
Outdoor Sensor
DHW Sensor
CH2
Thermostat
6 5
System
Sensor
4 3
Modulation
Signal
-+
2 1
CH2
Thermosta
t
CH1
Thermostat
4 3
Outdoor
Sensor
2 1
DHW
Sensor or
Aquastat
2 1
Modbus
+ G -
3 2 1
X7X4
X6X5
External Limit
Terminals
Manual Auto
Z.V.
Z.V.
Line Voltage Terminals
L N G L N G L N G L N G
FLAME POWER SUPPLY
CH PUMP
DHW PUMP
Please contact Triangle Tube’s technical support for more information on the possible use
of the Preset Pump Config function for this system.
NOTICE
46
CHAPTER 5
CHAPTER 5 - BOILER SETTINGS
Fig. 20 -INSTINCT Combi - System Piping - Multi Zone Valve - Single Circulator
INSTINCT COMBI - PUMP SETTINGS
Heat Call DHW pump CH pump Flame
CH1 OFF ON ON
CH2 OFF ON ON
DHW ON ON OFF
CTRLMax_w Instinct_UK version_222171_A01.indd 46 18/07/2019 18:38