CTRLMax Manual
27
CHAPTER 5
CHAPTER 5 - BOILER SETTINGS
The WP di trigger parameter is the required pressure
change when the internal pump of a HeatMaster is starting.
This function allows to detect the correct operation of the
appliance internal pump.
Adjust the Modbus Address value using the LEFT or RIGHT
keys, then store the setting with the OK key.
HeatMaster TC Default: 290cpsi
Prestige/Instinct Default: 0cpsi (function not used in Pres-
tige and Instinct boilers)
Mix zone high limit
114°F
68°F 176°F
WP di trigger
0cpsi
0cpsi 725cpsi
Appliance Setting
B121
Appliance Setting
Enter appliance code
[0]XXX
Verify appliance code
Press Installer button to conrm
B122
Appliance setting
WAIT
Boiler Settings
Boiler Settings
Prestige Model Prestige Solo
Lockout Temp. 210°F [99°C]
Modbus Address 0=BCST
Pump settings
Ignition Level 3500rpm
Mix zone high limit 114°F
Boiler Settings
Modbus Address 0=BCST
Pump settings
Ignition Level 3500rpm
Mix zone high limit 114°F
WP di trigger 0pcsi
Appliance setting
Boiler Settings
Lockout Temp. 210°F [99°C]
Modbus Address 0=BCST
Pump settings
Ignition Level 3500rpm
Mix zone high limit 114°F
WP di trigger 0pcsi
The Mix zone high limit setting allows to limit the maxi-
mum temperature in the mixed circuit. The function works
like an Overheat Cut-o Activation of the limit and will cause
the appliance to go in fault state (lockout). This setting allows
to change the limit temperature for the mixed circuit.
Be aware that for Floor Heating systems this tem-
perature may NOT be adjusted. A higher tempera-
ture setting may damage your floor heating circuit
Adjust the Mix Zone High Limits value using the LEFT or
RIGHT keys, then store the setting with the OK key.
Default: 114°F
NOTICE
The Appliance Setting allows to change the appliance
type and model using a specic code. The appliance type
and model are factory preset for the appliance you have
received. This means that parameters are already set for the
appliance, and the appliance type MAY NOT be changed,
unless the CTRLMax mainboard is replaced or repaired, or a
gas conversion is made to the appliance.
If the appliance type needs to be entered, please refer to the
appliance code written on the data plate located at the side
of the boiler.
Increase/decrease the value (from 0 to 9, then A to Z) using
the UP or DOWN keys to, then change position with the
LEFT or RIGHT keys.
Once the code has been entered, conrm the code by
pressing OK, then follow the instructions displayed on the
screen: press the installer button (PRESTIGE/HEATMASTER),
or touch the UP key (INSTINCT).
Actuate the UP, DOWN, LEFT or RIGHT keys to go back
to the previous screen and change the code if you made a
mistake when entering the code.
The software will then process the change and return to
the Main screen.